686
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
MFAO Signal Level
Ub-15
(878E)
Previous Fault MMDD
Displays the month and day of the previous fault.
Unit: -
No signal output available
Ub-16
(878F)
Previous Fault HHMM
Displays the hour and minute of the previous fault.
Unit: -
No signal output available
Ub-17
(8790)
Contactor Voltage
Displays the measured voltage for the power going to the contactor coils.
Unit: 1 Vac
No signal output available
Ub-18
(8791)
Software Version
Displays the software version currently programmed into the bypass.
Unit: -
No signal output available
Ub-19
(8792)
Date Year YYYY
Displays the current year.
Unit: -
No signal output available
Ub-20
(8793)
Date Month Day MMDD
Displays the current date (Month and Date).
Unit: -
No signal output available
Ub-21
(8794)
Time Hour Min HHMM
Displays the current time (Hours and Minutes).
Unit: -
No signal output available
Ub-22
(8795)
Bypass Analog Input
Bypass MFAI level
Unit: 0-100%
No signal output available
Ub-23
(8796)
Motor 1 Overload
Motor 1 Overload level
Unit: 0-100%
No signal output available
Ub-24
(8797)
Motor 2 Overload
Motor 2 Overload level
Unit: 0-100%
No signal output available
Ub-94
(87DD)
Bypass CPU Usage
Current Bypass CPU Load
Unit: 0-100%
No signal output available
Ub-95
(87DE)
Line Frequency
Calculated AC line frequency
Unit: Hz
No signal output available
Ub-96
(87DF)
Byp Phase Loss Level
Current Phase Loss level
Unit: 0-100%
No signal output available
Ub-99
(87E2)
Expert
Desired HV600 software
version
Shows the latest version of HV600 software that this version of HV600 Bypass software supports.
Unit: -
No signal output available
◆
UC: BACnet Diagnostic Monitors
No.
(Hex.)
Name
Description
MFAO Signal Level
UC-01
(3DB0)
BN MSTP Net Health
Shows a number between 0.0% and 100.0% that identifies the health of the MSTP network. This
number is dependent on the number of CRC errors, token losses, token retries, and net deadtime
perceived.
Unit: 0.1%
No signal output available
UC-02
(3DB1)
BACnet Tokens Rx
Shows the number of received MSTP Tokens after you energize the drive.
Unit: 1
No signal output available
UC-03
(3DB2)
BACnet Tokens Tx
Shows the number of transmitted MSTP Tokens after you energize the drive.
Unit: 1
No signal output available
UC-04
(3DB3)
BACnet Messages Rx
Shows the number of messages with data (non-token, non-polling) received by the drive.
Unit: 1
No signal output available
UC-05
(3DB4)
BACnet Messages Tx
Shows the number of messages with data (non-token, non-polling) transmitted by the drive.
Unit: 1
No signal output available
UC-06
(3DB5)
MSTP Next Node Addr
Shows the next known node in the MSTP loop. This is the node to which the drive will pass the
token.
Unit: Hex
No signal output available
UC-07
(3DB6)
MSTP Prev Node Addr
Shows the previous known node in the MSTP loop. This is the node from which the drive received
the token.
Unit: Hex
No signal output available
UC-08
(3DB7)
MSTP H MAC Found
Shows the highest MAC address found on the network. This will report the highest value MAC
address to which the token was passed by any node on the MSTP loop.
Unit: Hex
No signal output available
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...