7.6 480 V Enclosed Model Specifications
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
537
7.6
480 V Enclosed Model Specifications
Table 7.11 480 V Enclosed Ratings
Model
B001
B002
B003
B004
B007
B011
B014
Maximum Applicable Motor Output (HP)
0.75
1
2
3
5
7.5
10
Input
Rated Input Current (A)
2.2
2.7
4.0
5.4
8.2
11.6
14.6
Rated Voltage
Rated Frequency
Three-Phase 480 Vac 50/60 Hz
Allowable Voltage
Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Output
Rated Output Current (A)
1.6
2.1
3.4
4.8
7.6
11.0
14.0
Minimum Applicable
Motor Current (A)
1.5
1.5
1.5
1.5
1.5
1.5
3.75
Overload Tolerance
110% of rated output current for 60 s
150% peak
Carrier Frequency
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage
(V)
Three-Phase 480 Vac
Maximum Output
Frequency (Hz)
240 Hz
Harmonics
Reduction
Input Power (kVA)
Built-in
EMC
Filter (IEC/EN 61800-3
Category 2)
Built-in
*1
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output current of
the drive output amps must be equal to or more than the motor rated current.
*3
Carrier frequency is 5 kHz. You must derate the current to increase the carrier frequency.
Table 7.12 480 V Enclosed Ratings
Model
B021
B027
B034
B040
B052
B065
B077
Maximum Applicable Motor Output (HP)
15
20
25
30
40
50
60
Input
Rated Input Current (A)
21.6
27.6
35.0
41.0
53.0
66.0
78.0
Rated Voltage
Rated Frequency
Three-Phase 480 Vac 50/60 Hz
Allowable Voltage
Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Output
Rated Output Current (A)
21.0
27.0
34.0
40.0
52.0
65.0
77.0
Minimum Applicable
Motor Current (A)
3.75
3.75
7.5
7.5
7.5
7.5
15
Overload Tolerance
110% of rated output current for 60 s
150% peak
Carrier Frequency
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage
(V)
Three-Phase 480 Vac
Maximum Output
Frequency (Hz)
240 Hz
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...