SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
435
Note:
Actual values depend on unit settings of drive parameters
o1-03, o1-09, o1-10, and o1-11
.
■
Z1-18: Energy Savings Output Cur Level
No.
(Hex.)
Name
Description
Default
(Range)
Z1-18
(85D7)
Energy Savings Output Cur
Level
Lets the system switch when the output current is more than this level of motor rated current for the
time set in Z1-22, Energy Time.
0.0%
(0.0 - 100.0%)
■
Z1-19: Energy Savings Fref Deadband
No.
(Hex.)
Name
Description
Default
(Range)
Z1-19
(85D8)
Energy Savings Fref
Deadband
Sets the tolerance around the drive frequency reference value during comparisons to enter or exit
Energy Savings Mode.
0.50 Hz
(0.00 - 5.00 Hz)
■
Z1-20: Energy Savings Out Freq Deadband
No.
(Hex.)
Name
Description
Default
(Range)
Z1-20
(85D9)
Energy Savings Out Freq
Deadband
Sets the tolerance around the drive output frequency value during comparisons to enter or exit Energy
Savings Mode.
0.50 Hz
(0.00 - 5.00 Hz)
■
Z1-21: Energy Savings Out Cur Deadband
No.
(Hex.)
Name
Description
Default
(Range)
Z1-21
(85DA)
Energy Savings Out Cur
Deadband
Sets the tolerance around the drive output current value during comparisons to enter or exit Energy
Savings Mode as a percentage of motor rated current.
15.0%
(0.0 - 30.0%)
■
Z1-22: Energy Savings Mode Time
No.
(Hex.)
Name
Description
Default
(Range)
Z1-22
(85DB)
Energy Savings Mode Time
Sets the length of time that the drive frequency reference and drive output frequency must be in the
set limits before transferring to Energy Savings Mode.
30 s
(10 - 3600 s)
■
Z1-23: Energy Savings Freq Ref Increase
No.
(Hex.)
Name
Description
Default
(Range)
Z1-23
(85DC)
Energy Savings Freq Ref
Increase
Sets the value to add to the drive Frequency Reference when transferring to Bypass Energy Savings
Mode.
6.00 Hz
(0.00 - 10.00 Hz)
Note:
Actual values depend on unit settings of drive parameters
o1-03, o1-09, o1-10, and o1-11
.
■
Z1-24: Contactor Open Delay
No.
(Hex.)
Name
Description
Default
(Range)
Z1-24
(85DD)
Contactor Open Delay
Sets the time to delay after commanding the drive output contactor K2 or bypass contactor K3 or 2-
Motor OR/AND contactors K4 and K5 to open to let the contacts open.
0.2 s
(0.0 - 5.0 s)
■
Z1-25: Contactor Close Delay
No.
(Hex.)
Name
Description
Default
(Range)
Z1-25
(85DE)
Contactor Close Delay
Sets the time to delay after commanding the drive output contactor K2 or bypass contactor K3 or 2-
Motor OR/AND contactors K4 and K5 to close to let the contacts close.
0.2 s
(0.0 - 5.0 s)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...