398
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 5.64 Faults Ignored during Emergency Override
Faults
bAT [Keypad Battery Low Voltage]
bCE [Bluetooth Communication Error]
bUS [Option Communication Error]
CE [Modbus Communication Error]
CoF [Current Offset Fault]
dEv [Speed Deviation]
EF0 [Option Card External Fault]
EF1 - EF7 [External Fault (Terminal Sx)]
Err [EEPROM Write Error]
FAn1 [Drive Cooling Fan Fault]
HLCE [High Level Communications Error]
LF [Output Phase Loss]
LF2 [Output Current Imbalance]
MSL [Net Master Lost]
nSE [Node Setup Error]
OD [Output Disconnect]
oH3 [Motor Overheat (PTC Input)]
oH4 [Motor Overheat Fault (PTC Input)]
Faults
oL1 [Motor Overload]
oL2 [Drive Overloaded]
oL3 [Overtorque Detection 1]
oL4 [Overtorque Detection 2]
oL7 [High Slip Braking Overload]
oPr [Keypad Connection Fault]
oS [Overspeed]
ov2 [DC Bus Overvoltage 2]
PE1 [PLC Fault 1]
PE2 [PLC Fault 2]
PF [Input Phase Loss]
TiM [Keypad Time Not Set]
UL3 [Undertorque Detection 1]
UL4 [Undertorque Detection 2]
UL6 [Underload or Belt Break Detected]
Uv1 [DC Bus Undervoltage]
VLTS [Thermostat Fault]
Note:
•
During Emergency Override, the drive will not prevent
oH [Heatsink Overheat]
and
oH1 [Heatsink Overheat]
faults. The drive will Auto
Restart when
U4-08 [Heatsink Temperature]
is less than
L8-02 [Overheat Alarm Level]
for
oH
faults, or the drive Overheat Pre-Alarm
Level for
oH1
faults.
•
Emergency Override Fault Activation Bits set in
S6-11 [EMOVR Drive Protection Fault ON]
to
S6-14 [EMOVR Application 1 Fault ON]
enable the fault detection for the above functions, if necessary.
During Emergency Override, the drive ignores the alarms in
when
S6-07 = 0
:
Table 5.65 Alarms Ignored during Emergency Override
Alarms
bUS [Option Communication Error]
CE [Modbus Communication Error]
dnE [Drive Disabled]
INTLK [BAS Interlock]
oH3 [Motor Overheat (PTC Input)]
oL3 [Overtorque Detection 1]
Alarms
oL4 [Overtorque Detection 2]
SAFE [Customer Safeties]
UL3 [Undertorque Detection 1]
UL4 [Undertorque Detection 2]
UL6 [Underload or Belt Break Detected]
The drive ignores these alarms, but it enables these MFDO functions during Emergency Override operation:
•
H2-xx = B [MFDO Function Selection = Torque Detection 1 (N.O.)]
•
H2-xx = 17 [Torque Detection 1 (N.C.)]
•
H2-xx = 18 [Torque Detection 2 (N.O.)]
•
H2-xx = 19 [Torque Detection 2 (N.C.)]
•
H2-xx = 58 [UL6 Underload Detected]
Emergency Override Test Mode
Emergency Override Test Mode lets you test Emergency Override operation while all drive faults stay enabled.
Parameter
S6-07 [EMOVR Fault Suppression Mode]
controls this function.
To test Emergency Override operation, use this procedure:
1. Set
S6-07 = 1 [Test Mode]
.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...