YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
305
■
H4-03: Terminal FM Analog Output Bias
No.
(Hex.)
Name
Description
Default
(Range)
H4-03
(041F)
RUN
Terminal FM Analog Output
Bias
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the FM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-
07 [Terminal FM Signal Level Select]
.
■
H4-04: Terminal AM Analog Output Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-04
(0420)
Terminal AM Analog Output
Select
Sets the monitoring number to be output from the MFAO terminal AM.
103
(000 - 999)
Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H4-04 = 103
to monitor
U1-03 [Output Current]
.
Note:
When you use the terminal in through mode, set this parameter to
000
or
031.
You can set the terminal AM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
■
H4-05: Terminal AM Analog Output Gain
No.
(Hex.)
Name
Description
Default
(Range)
H4-05
(0421)
RUN
Terminal AM Analog Output
Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
50.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-
08 [Terminal AM Signal Level Select]
.
Example settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
•
H4-04 = 103 [Terminal AM Analog Output Select = Output Current]
•
H4-05 = 50.0%
•
H4-06 = 0.0% [Terminal AM Analog Output Bias = 0.0%]
•
H4-08 = 0 [0 to 10 V]
■
H4-06: Terminal AM Analog Output Bias
No.
(Hex.)
Name
Description
Default
(Range)
H4-06
(0422)
RUN
Terminal AM Analog Output
Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-
08 [Terminal AM Signal Level Select]
.
■
H4-07: Terminal FM Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-07
(0423)
Terminal FM Signal Level
Select
Sets the MFAO terminal FM output signal level.
0
(0, 2)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...