80
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L3-23
(04FD)
Stall P Reduction at
Constant HP
Sets the function to automatically decrease the Stall Prevention Level during Run for
constant output ranges.
0 : Use L3-06 for Entire Speed Range
1 : Automatic Reduction @ CHP Region
0
(0, 1)
L3-24
(046E)
Expert
Motor Accel Time @
Rated Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque
for stopped single-drive motors.
Determined by o2-04, E2-
11, and E5-01
(0.001 - 10.000 s)
L3-25
(046F)
Expert
Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
1.0
(0.1 - 1000.0)
L3-26
(0455)
Expert
Additional DC Bus
Capacitors
Sets the capacity for external main circuit capacitors. Usually it is not necessary to change
this setting. Sets this parameter when you use the KEB Ride-Thru function.
0 μF
(0 to 65000 μF)
L3-27
(0456)
Stall Prevention
Detection Time
Sets a delay time between reaching the Stall Prevention level and starting the Stall
Prevention function.
50 ms
(0 - 5000 ms)
L3-35
(0747)
Expert
Speed Agree Width for
Auto Decel
Sets the width for speed agreement when
L3-04 = 2 [Decel Stall Prevention Selection =
Automatic Decel Reduction]
. Usually it is not necessary to change this setting.
0.00 Hz
(0.00 - 1.00 Hz)
◆
L4: Speed Detection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L4-01
(0499)
Speed Agree Detection
Level
Sets the level to detect speed agree or motor speed when
H2-01 to H2-03 = 2, 3, 4, 5
[MFDO Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency
Detection 1, Frequency Detection 2]
.
0.0 Hz
(0.0 - 400.0 Hz)
L4-02
(049A)
Speed Agree Detection
Width
Sets the width to detect speed agree or motor speed when
H2-01 to H2-03 = 2, 3, 4, 5
[MFDO Function Selection = Speed Agree 1, User-set Speed Agree 1, Frequency
Detection 1, Frequency Detection 2]
.
2.0 Hz
(0.0 - 20.0 Hz)
L4-03
(049B)
Speed Agree Detection
Level (+/-)
Sets the speed agree detection level or motor speed detection level when
H2-01 to H2-03 =
13, 14, 15, 16 [MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2,
Frequency Detection 3, Frequency Detection 4]
.
0.0 Hz
(-400.0 - +400.0 Hz)
L4-04
(049C)
Speed Agree Detection
Width (+/-)
Sets the width to detect speed agree or motor speed when
H2-01 to H2-03 = 13, 14, 15, 16
[MFDO Function Selection = Speed Agree 2, User-set Speed Agree 2, Frequency
Detection 3, Frequency Detection 4]
.
2.0 Hz
(0.0 - 20.0 Hz)
L4-05
(049D)
Fref Loss Detection
Selection
Sets the operation when the drive detects a loss of frequency reference.
0 : Stop
1 : Run at (L4-06 x Last Reference)
1
(0, 1)
L4-06
(04C2)
Frequency Reference
@Loss of Ref
Sets the frequency reference as a percentage to continue drive operation after it detects a
frequency reference loss. The value is a percentage of the frequency reference before the
drive detected the loss.
80.0%
(0.0 - 100.0%)
L4-07
(0470)
Speed Agree Detection
Selection
Sets the condition that activates speed detection.
0 : No Detection during Baseblock
1 : Detection Always Enabled
0
(0, 1)
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...