YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
367
■
L3-24: Motor Accel Time @ Rated Torque
No.
(Hex.)
Name
Description
Default
(Range)
L3-24
(046E)
Expert
Motor Accel Time @ Rated
Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque for
stopped single-drive motors.
Determined by o2-04, E2-11,
and E5-01
(0.001 - 10.000 s)
Set one of these parameters to enable
L3-24
:
•
L2-29 = 1 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2]
•
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
•
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
•
H1-xx = 7A or 7B [MFDI Function Selection = KEB Ride-Thru 2 Activate (N.O./N.C.)]
Note:
When Auto-Tuning changes the value of
E2-11 [Motor Rated Power]
, the drive will automatically set
L3-24
to the value for a Yaskawa
standard motor (4 poles). When you use a PM motor, the drive uses the value in
E5-01 [PM Motor Code Selection]
to change
L3-24
.
Manually Adjust Parameters
Use this formula to find the motor acceleration time:
•
J
Motor
= Moment of inertia of motor (kg m
2
)
•
n
rated
= Motor rated speed (min
-1
, r/min)
•
T
rated
= Motor rated torque (N∙m)
The rated torque is calculated using the following expression.
P
Motor
= Motor Rated Power (kW)
■
L3-25: Load Inertia Ratio
No.
(Hex.)
Name
Description
Default
(Range)
L3-25
(046F)
Expert
Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
1.0
(0.1 - 1000.0)
Set one of these parameters to enable
L3-25
:
•
L2-29 = 1 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2]
•
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
•
L3-11 = 1 [Overvoltage Suppression Select= Enabled]
•
H1-xx = 7A or 7B [MFDI Function Selection = KEB Ride-Thru 2 Activate (N.O./N.C.)]
Note:
•
If you set this value incorrectly when
L2-29 = 1
,
H1-xx = 7A or 7B
, or
L3-11 = 1
, it can cause large current ripples and
ov [Overvoltage]
,
Uv1 [DC Bus Undervoltage]
, or
oC [Overcurrent]
faults.
•
KEB Tuning will automatically set this value.
Manually Adjust Parameters
Use this formula to find the load inertia ratio:
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...