276
YASKAWA
TOEPYAIHV6002A HV600 Drive Programming
■
F7-23 to F7-32: Dynamic Out Param 1 to 10 for CommCard
No.
(Hex.)
Name
Description
Default
(Range)
F7-23 to F7-27
(03FB - 03FF)
F7-28 to F7-32
(0370 - 0374)
Dynamic Out Param 1 to 10
for CommCard
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a ProfiNet option, set
F7-23
to
F7-27
to configurable Output 1-
5.
0
■
F7-33 to F7-42: Dynamic In Param 1 to 10 for CommCard
No.
(Hex.)
Name
Description
Default
(Range)
F7-33 to F7-42
(0375 - 037E)
Dynamic In Param 1 to 10
for CommCard
When you use an Ethernet/IP option, sets Input Assembly 166. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set
F7-33
to
F7-37
to configurable inputs 1-5.
0
V/f
OLV/PM
OLV/PM
EZOLV
V/f
OLV/PM
OLV/PM
EZOLV
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 16: ...i 3 Warranty Information 16 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 158: ...1 22 Defaults by o2 04 Drive Model kVA Selection 158 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...
Страница 506: ...2 14 Y Application Features 506 YASKAWA TOEPYAIHV6002A HV600 Drive Programming...