4.4
Auto-Tuning
Auto-Tuning uses motor characteristics to automatically set parameters for vector control. Think about the type of
motor and the motor installation environment and select the best Auto-Tuning method.
The keypad will show the messages with prompts to input the necessary parameter information.
◆
Auto-Tuning for Induction Motors
This section gives information about Auto-Tuning for induction motors. Auto-Tuning sets motor parameters
E1-xx,
E2-xx
.
Note:
Do Stationary Auto-Tuning if you cannot do Rotational Auto-Tuning. There can be large differences between the measured results and the
motor characteristics when Auto-Tuning is complete. Examine the parameters for the measured motor characteristics after you do Stationary
Auto-Tuning.
Table 4.5 Types of Auto-Tuning for Induction Motors
Mode
Parameter Settings
Application Conditions and Benefits
Rotational Auto-Tuning
T1-01 = 0
•
When you can decouple the motor and load the motor can rotate freely while Auto-
Tuning.
•
When operating motors that have fixed output characteristics.
•
When it is necessary to use motors that have high-precision control.
•
When you cannot decouple the motor and load, but the motor load is less than 30%.
Line-to-Line Resistance
T1-01 = 2
•
After Auto-Tuning, the wiring distance between the drive and motor changed by 50
m or more.
•
When the wiring distance is 50 m or more in the V/f Control mode.
•
When the motor output and drive capacity are different.
■
Input Data for Induction Motor Auto-Tuning
To do Auto-Tuning, input data for the items in
that have an "x". Before starting Auto-Tuning, prepare the
motor test report or record the information on the motor nameplate as a reference.
Table 4.6 Input Data for Induction Motor Auto-Tuning
Input Data
Parameter
Unit
Auto-Tuning Mode
(T1-01 Setting)
Rotational Auto-Tuning
(0)
Line-to-Line Resistance
(2)
Motor Rated Power
T1-02
kW
x
x
Motor Rated Voltage
T1-03
V
x
-
Motor Rated Current
T1-04
A
x
x
Motor Base Frequency
T1-05
Hz
x
-
Number of Motor Poles
T1-06
-
x
-
Motor Base Speed
T1-07
min
-1
x
-
Motor Iron Loss
T1-11
W
x
-
◆
Precautions before Auto-Tuning
Examine the topics in this section before you start Auto-Tuning.
■
Prepare for Basic Auto-Tuning
•
You must input data from the motor nameplate or motor test report to do Auto-Tuning. Make sure that this data is
available before Auto-Tuning.
•
For best performance, make sure that the input supply voltage is equal to or more than the motor rated voltage.
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...