186
YASKAWA
TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
7.5
d: Reference Settings
◆
d1: Frequency Reference
No.
(Hex.)
Name
Description
Default
(Range)
d1-01
(0280)
RUN
Reference 1
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection
.
0.00 Hz
(0.00 - 400.00 Hz)
d1-02
(0281)
RUN
Reference 2
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
d1-03
(0282)
RUN
Reference 3
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
d1-04
(0283)
RUN
Reference 4
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
d1-05
(0284)
RUN
Reference 5
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
d1-06
(0285)
RUN
Reference 6
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
d1-07
(0286)
RUN
Reference 7
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
d1-08
(0287)
RUN
Reference 8
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 400.00 Hz)
d1-17
(0292)
RUN
Jog Reference
Sets the Jog frequency reference in the units from
o1-03 [Frequency Display Unit Selection]
. Set
H1-
xx = 6 [MFDI Function Selection = Jog Reference Selection]
to use the Jog frequency reference.
6.00 Hz
(0.00 - 400.00 Hz)
◆
d2: Reference Limits
No.
(Hex.)
Name
Description
Default
(Range)
d2-01
(0289)
Frequency Reference Upper
Limit
Sets maximum limit for all frequency references. The maximum output frequency is 100%.
100.0%
(0.0 - 110.0%)
d2-02
(028A)
Frequency Reference Lower
Limit
Sets minimum limit for all frequency references. The maximum output frequency is 100%.
0.0%
(0.0 - 110.0%)
d2-03
(0293)
Analog Frequency Ref
Lower Limit
Sets the lower limit for the master frequency reference (the first frequency of the multi-step speed
reference) as a percentage. The maximum output frequency is 100%.
0.0%
(0.0 - 110.0%)
◆
d3: Jump Frequency
No.
(Hex.)
Name
Description
Default
(Range)
d3-01
(0294)
Jump Frequency 1
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
d3-02
(0295)
Jump Frequency 2
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
d3-03
(0296)
Jump Frequency 3
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(0.0 - 400.0 Hz)
d3-04
(0297)
Jump Frequency Width
Sets the width of the frequency band that the drive will avoid.
1.0 Hz
(0.0 - 20.0 Hz)
Содержание HV600
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 20: ...1 2 Catalog Code and Nameplate Check 20 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 34: ...2 7 Removing Reattaching Covers 34 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 40: ...Page Intentionally Blank...
Страница 154: ...5 11 Diagnosing and Resetting Faults 154 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 170: ...6 7 Periodic Inspection and Maintenance 170 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 266: ...7 16 U Monitors 266 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...
Страница 290: ...8 4 Other Embedded Communication Protocols 290 YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation Startup...