YASKAWA
TOEPC71061732E HV600 Drive Installation & Primary Operation
63
◆
Switches and Jumpers on the Terminal Board
The terminal board has switches to adapt the drive I/Os to the external control signals as shown in
Set the switches to select the functions for each terminal.
Figure 10.8 Locations of Switches
Table 10.8 I/O Terminals and Switches Functions
Position
Switch
Terminal
Function
Default Setting
A
Jumper switch S1
A1, A2
Sets terminals A1 and A2 to voltage or current output.
A1: V (voltage input)
A2: I (current input)
B
Jumper switch S5
FM, AM
Sets terminals FM and AM to voltage or current output.
FM: V (voltage output)
AM: V (voltage output)
C
DIP switch S2
-
Enables and disables the termination resistor of these
communications:
•
APOGEE FLN
•
BACnet
•
MEMOBUS/Modbus
•
Metasys N2
OFF
◆
Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
•
MFDI (terminals S1 to S7)
•
MFDO (terminals M1 to M6)
•
MFAI (terminals A1, A2)
•