YASKAWA
TOEPC71061732E HV600 Drive Installation & Primary Operation
11
No.
Description
5
EMC filter
C: Built-in EMC filter for C2
6
Protection design
•
B: IP20/UL Open Type
•
F: IP20/UL Type 1
•
V: IP55/UL Type 12
7
Environmental specification
A: Standard
■
Rated Output Current
and
give the rated output current values.
Note:
•
These output current values are applicable for drives that operate at standard specifications.
•
Derate the current in applications that:
–
Increase the carrier frequency
–
Have high ambient temperature
–
Use side-by-side installation.
Table 4.2 Output Current for Three-Phase AC 208 V Class Models (NEMA Rating)
Model
Maximum Applicable Motor Output
kW (HP)
Rated Output Current
A
2011
2.2 (3)
10.6
2017
3.7 (5)
16.7
2024
5.5 (7.5)
24.2
2031
7.5 (10)
30.8
2046
11 (15)
46.2
2059
15 (20)
59.4
2075
18.5 (25)
74.8
2088
22 (30)
88
2114
30 (40)
114
2143
37 (50)
143
2169
45 (60)
169
2211
55 (75)
211
2273
75 (100)
273
Table 4.3 Output Current for Three-Phase AC 480 V Class Models (NEMA Rating)
Model
Maximum Applicable Motor Output
kW (HP)
Rated Output Current
A
4005
2.2 (3)
4.8
4008
3.7 (5)
7.6
4011
5.6 (7.5)
11
4014
7.5 (10)
14
4021
11.2 (15)
21
4027
15 (20)
27
4034
18.6 (25)
34
4040
22 (30)
40
4052
30 (40)
52
4065
37 (50)
65
4077
45 (60)
77