650
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S2-19
(3218)
Timer 4 Sequence
Selection
Sets the drive response when sequence timer 4 is active.
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
0
(0 - 2)
S2-20
(3219)
Timer 4 Reference Source Selects the frequency reference source to run the drive when sequence timer 4 is active
(only applicable when
S2-19 > 0 [Timer 4 Sequence Selection ≠ Digital Out Only]
).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use
d1-xx
frequency reference when PID
mode is disabled and
YA-xx
setpoint when PID is enabled.
0
(0 - 8)
◆
S3: PI2 Control
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S3-01
(321A)
PI2 Control Enable
Selection
Sets when the PI Auxiliary Control function is enabled:
0 : Disabled
1 : Always
2 : Drive Running
3 : Motor Running
0
(0 - 3)
S3-02
(321B)
RUN
PI2 Control Transducer
Scale
Sets the full scale (10 V or 20 mA) output of the pressure transducer that is connected to
the analog input terminals programmed for PI2 (Setpoint or Feedback).
Note:
Parameters
S3-04 [PI2 Control Unit Selection]
,
S3-03 [PI2 Control Decimal Place
Pos]
, and
S3-02 [PI2 Control Transducer Scale]
set the unit, resolution, and upper
limit.
100.00
(1.00 - 600.00)
S3-03
(321C)
RUN
PI2 Control Decimal
Place Pos
Sets the decimal place display for secondary PI units.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
2
(0 - 3)
S3-04
(321D)
RUN
PI2 Control Unit
Selection
Sets the units displayed for the PI2 Control parameters and monitor.
0 :
“
WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 :
“
Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(S3-18~20)
50 : None
48
(0 - 50)
S3-05
(321E)
RUN
PI2 Control Setpoint
Sets the PI2 Control target setpoint.
Note:
Parameters
S3-04 [PI2 Control Unit Selection]
,
S3-03 [PI2 Control Decimal Place
Pos]
, and
S3-02 [PI2 Control Transducer Scale]
set the unit, resolution, and upper
limit.
0.00
(0.00 - 600.00)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...