YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
489
Code
Name
Causes
Possible Solutions
oH1
Heatsink Overheat
The ambient temperature is high and the heatsink
temperature of the drive is more than the
oH1
detection level.
•
Measure the ambient temperature.
•
Increase the airflow in the control panel.
•
Install a cooling device (cooling fan or air conditioner) to lower
the ambient temperature.
•
Remove objects near the drive that are producing too much heat.
The load is too heavy.
•
Measure the output current.
•
Decrease the load.
•
Decrease the value set in
C6-02 [Carrier Frequency Selection]
.
Note:
•
The drive detects this fault if the heatsink temperature of the drive is more than the
oH1
detection level.
o2-04 [Drive Model (KVA) Selection]
determines the
oH1
detection level.
•
Do a Fault Reset to clear the fault.
•
L5-08 [Fault Reset Enable Select Grp2]
disables the Auto Restart function.
Code
Name
Causes
Possible Solutions
oH3
Motor Overheat (PTC Input)
The thermistor wiring that detects motor temperature
is defective.
Correct wiring errors.
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault
The motor has overheated.
•
Check the load level, acceleration/deceleration time, and motor
start/stop frequency (cycle time).
•
Decrease the load.
•
Increase the values set in
C1-01 to C1-04 [Acceleration/
Deceleration Times]
.
•
Set
E2-01 [Motor Rated Current (FLA)]
correctly to the value
specified by the motor nameplate.
•
Make sure that the motor cooling system is operating correctly,
and repair or replace it if it is damaged.
•
Adjust
E1-04 to E1-10 [V/f Pattern Parameters]
. Decrease the
values set in
E1-08 [Mid Point A Voltage]
and
E1-10 [Minimum
Output Voltage]
.
Note:
If the values set in
E1-08
and
E1-10
are too low, the overload
tolerance will decrease at low speeds.
Note:
•
When
H3-02 or H3-10 = E [MFAI Function Selection = Motor Temperature (PTC Input)]
, the drive detects this fault if the motor overheat signal entered to analog input terminals
A1 or A2 is more than the alarm detection level.
•
Do a Fault Reset to clear the fault.
•
If the drive detects this fault, it will operate the motor as specified by the Stopping Method set in
L1-03 [Motor Thermistor oH Alarm Select]
.
Code
Name
Causes
Possible Solutions
oH4
Motor Overheat Fault (PTC Input)
The motor has overheated.
•
Check the load level, acceleration/deceleration time, and motor
start/stop frequency (cycle time).
•
Decrease the load.
•
Increase the values set in
C1-01 to C1-04 [Acceleration/
Deceleration Times]
.
•
Set
E2-01 [Motor Rated Current (FLA)]
correctly to the value
specified by the motor nameplate.
•
Make sure that the motor cooling system is operating correctly,
and repair or replace it if it is damaged.
•
Adjust
E1-04 to E1-10 [V/f Pattern Parameters]
. Decrease the
values set in
E1-08 [Mid Point A Voltage]
and
E1-10 [Minimum
Output Voltage]
.
Note:
If
E1-08
and
E1-10
are set too low, the overload tolerance will
decrease at low speeds.
Note:
•
The drive detects this fault if the motor overheat signal that was entered to an analog input terminals A1or A2 is more than the alarm detection level. (If
H3-02 or H3-10= E [MFAI
Function Select = Motor Temperature (PTC Input)]
was set.)
•
Do a Fault Reset to clear the fault.
Code
Name
Causes
Possible Solutions
oL1
Motor Overload
The load is too heavy.
Decrease the load.
Note:
Reset
oL1
when
U4-16 [Motor oL1 Level]
< 100.
The acceleration/deceleration times or cycle times are
too short.
•
Examine the acceleration/deceleration times and the motor start/
stop frequencies (cycle times).
•
Increase the values set in
C1-01 to C1-04 [Acceleration/
Deceleration Times]
.
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...