262
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
WARNING!
Crush Hazard. Make sure that the settings for H1-61 to H1-67 [Terminal Sx On-Delay Time] and H1-71 to H1-77
[Terminal Sx Off-Delay Time] are correct when you interface the drive with a safety process. The drive also applies the time delay
settings to the safety functions, for example, Emergency Override and Baseblock. Incorrect time delay settings can cause serious
injury or death from malfunction of the safety functions.
When the terminal is ON, the function set to that terminal activates after the ON-delay timer for the terminal is
expired. The terminal will reset the ON-delay timer when the terminal is OFF.
When the terminal is OFF and the function is active, the function will run until the OFF-delay timer is expired. The
terminal will reset the OFF-delay timer when the terminal is ON again.
The ON-delay and OFF-delay timers also have an effect on
U1-10 [Input Terminal Status]
. When the ON-delay is
expired and the function is active, the drive sets the applicable bits. When the OFF-delay is expired and the function
deactivates, the drive resets the bits.
Note:
The ON-delay timer does not apply when the inputs are ON at power-up.
shows drive operation when you apply ON/OFF-Delay Timers to the MFDI set for
H1-xx = 6E [HAND
Command]
in these conditions:
•
S5-02 = 1 [HAND/AUTO Switchover During Run = Enabled]
•
S5-04 ≠ 0 [HAND-OFF-AUTO Behavior ≠ Legacy]
Figure 5.39 Example of ON-Delay and OFF-Delay Timers
Inverse Multi-Function Digital Inputs
For inverse MFDIs (
H1-xx > 100
), the delay timers use the inverse condition of the digital input.
When a terminal is OFF, the function set to that terminal activates after the ON-delay timer for the terminal is expired.
The terminal will reset the ON-delay timer when the terminal is ON.
When the terminal is ON and the function is active, the function will run until the OFF-delay timer is expired. The
terminal will reset the OFF-delay timer when the terminal is OFF again.
Note:
If you change a terminal function selection between an inverse and a non-inverse digital input selection while an ON-delay or OFF-delay
timer is active, the new delay timer will not go into effect until the current ON-delay or OFF-delay timer is expired, and the digital input
changes to ON or OFF.
■
H1-61: Terminal S1 On-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H1-61
(39E1)
RUN
Terminal S1 On-Delay Time
Sets the length of time necessary for Terminal S1 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
■
H1-62: Terminal S2 On-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
H1-62
(39E2)
RUN
Terminal S2 On-Delay Time
Sets the length of time necessary for Terminal S2 to be closed before the drive does the programmed
function.
0.00 s
(0.00 - 300.00 s)
Содержание H6B1A002
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...