TOEPC71061737D GA800 DRIVE INSTALLATION & PRIMARY OPERATION
Table 12.4 Closed-Loop Crimp Terminals for 6-Phase/12-Pulse 400 V Class Drives (Drive Models: Txxx) (Manufacturer:
PANDUIT Corp.)
Model
Recomm. Gauge (AWG, kcmil)
Crimp Terminal
Model
R/L1, R1/L11
S/L2, S1/L21
T/L3, T1/L31
U/T1
V/T2
W/T3
-
+3
T103
-
-
-
-
4
P4-14R-E
S4-14R-E
T140, T168
-
-
-
-
4
P4-56R-E
S4-56R-E
T208
1/0 × 1 × 2
1/0 × 2P
1/0 × 2P
1/0 × 2P
-
S1/0-38R-X
-
-
-
-
4
P4-38R-E
S4-38R-E
T250
2/0 × 1 × 2
2/0 × 2P
-
-
-
S2/0-38R-X
-
-
1/0 × 2P
1/0 × 2P
-
S1/0-38R-X
-
-
-
-
2
P2-38R-X
S2-38R-X
T302
4/0 × 1 × 2
-
-
-
-
S4/0-38R-5
-
3/0 × 2P
-
-
-
S3/0-38R-5
-
-
1/0 × 2P
1/0 × 2P
-
S1/0-38R-X
-
-
-
-
2
P2-38R-X
S2-38R-X
T371
250 × 1 × 2
250 × 2P
-
-
-
S250-12R-5
-
-
3/0 × 2P
3/0 × 2P
-
S3/0-12R-5
-
-
-
-
1
S2-12R-X
T414
300 × 1 × 2
300 × 2P
-
-
-
LCA300-12-X
LCAX300-12-6
-
-
4/0 × 2P
4/0 × 2P
-
S4/0-12R-5
-
-
-
-
1
S2-12R-X
T477
2/0 × 2 × 2
-
-
-
-
S2/0-12R-X
-
4/0 × 4P
-
-
-
S4/0-12R-5
-
-
3/0 × 4P
3/0 × 4P
-
S3/0-12R-5
-
-
-
-
1/0
S1/0-12R-X
T568
3/0 × 2 × 2
-
3/0 × 4P
3/0 × 4P
-
S3/0-12R-5
-
4/0 × 4P
-
-
-
S4/0-12R-5
T605
4/0 × 2 × 2
-
4/0 × 4P
4/0 × 4P
-
S4/0-12R-5
-
300 × 4P
-
-
-
LCA300-12-X
LCAX300-12-6
-
-
-
-
2/0
S2/0-12R-X
T720
250 × 2 × 2
-
-
-
-
S250-12R-5
-
300 × 4P
-
-
-
LCA300-12-X
LCAX300-12-6
-
-
4/0 × 4P
4/0 × 4P
-
S4/0-12R-5
-
-
-
-
2/0
S2/0-12R-X
*1
For use with PANDUIT Corp. heat-shrinkable tubing HSTT-series or an equivalent UL-recognized heat-shrinkable tubing rated 600 V
minimum.