12.11 o: Keypad-Related Settings
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
989
Note:
Set this parameter in 10-hour (h) units. When
o4-01 = 30
,
U4-01 [Cumulative Ope Time] = 300 h
.
■
o4-02: Elapsed Operating Time Selection
No.
(Hex.)
Name
Description
Default
(Range)
o4-02
(050C)
Elapsed Operating Time
Selection
Sets the condition that counts the cumulative operation time.
0
(0, 1)
0 : U4-01 Shows Total Power-up Time
Counts the time from when the drive is energized to when it is de-energized.
1 : U4-01 Shows Total RUN Time
Counts the time that the drive outputs voltage.
■
o4-03: Fan Operation Time Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-03
(050E)
Fan Operation Time Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units.
0 h
(0 - 9999 h)
Use monitor
U4-03 [Cooling Fan Ope Time]
to view the total operation time of the cooling fan. When you replace a
cooling fan, set
o4-03 = 0
to reset
U4-03
. Select
o4-03
on the keypad to show the current value of
U4-03
in 10-hour
(h) units. If you use the monitor to change
o4-03
, the recount of
U4-03
starts with the
o4-03
setting.
Note:
The drive sets
o4-03
in 10-hour (h) units. When
o4-03 = 30
,
U4-03 [Cooling Fan Ope Time]
will show
“
300 h
”
.
■
o4-05: Capacitor Maintenance Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-05
(051D)
Capacitor Maintenance
Setting
Sets the
U4-05 [CapacitorMaintenance]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-05 = 0
to reset
U4-05
. When the
o4-05
setting changes, the count of
U4-05
starts
again as specified by the setting of
o4-05
. After you complete the configuration,
o4-05
automatically resets to
0
.
Note:
The maintenance period changes for different operating environments.
■
o4-07: Softcharge Relay Maintenance Set
No.
(Hex.)
Name
Description
Default
(Range)
o4-07
(0523)
Softcharge Relay
Maintenance Set
Sets the
U4-06 [PreChargeRelayMainte]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-07 = 0
to reset
U4-06
. When the
o4-07
setting changes, the count of
U4-06
starts
again as specified by the setting of
o4-07
. After you complete the configuration,
o4-07
automatically resets to
0
.
Note:
The maintenance period changes for different operating environments.
■
o4-09: IGBT Maintenance Setting
No.
(Hex.)
Name
Description
Default
(Range)
o4-09
(0525)
IGBT Maintenance Setting
Sets the
U4-07 [IGBT Maintenance]
monitor value.
0%
(0 - 150%)
When you replace a drive, set
o4-09 = 0
to reset
U4-07
. When the
o4-09
setting changes, the count of
U4-07
starts
again as specified by the setting of
o4-09
. After you complete the configuration,
o4-09
automatically resets to
0
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...