YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
921
shows the Stall Prevention during deceleration function.
Figure 12.134 Stall Prevention Operation during Deceleration
2 : Intelligent (Ignore Decel Ramp)
The drive adjusts the deceleration rate to keep the DC bus voltage at the
L3-17 [DC Bus Regulation Level]
level. This
makes the shortest possible deceleration time and will not let the motor stall. The drive ignores the selected
deceleration time and the possible deceleration time cannot be less than 1/10 of the set deceleration time.
This function uses these parameters to adjust the deceleration rate:
•
L3-20 [DC Bus Voltage Adjustment Gain]
•
L3-21 [OVSuppression Accel/Decel P Gain]
•
L3-24 [Motor Accel Time @ Rated Torque]
•
L3-25 [Load Inertia Ratio]
Note:
The deceleration time is not constant. For applications where the precision of the stop position is very important, use a dynamic braking
option and set
L3-04 = 0
. If an
ov
occurs, set
L3-04 = 3
.
3 : General Purpose w/ DB resistor
A braking resistor is necessary for this setting. The braking resistor and the drive work together for the Stall
Prevention during deceleration function.
4 : Overexcitation/High Flux
Enables Overexcitation/High Flux and enables a shorter deceleration time than when
L3-04 = 0
.
Note:
•
If the overexcitation time is long and you decelerate frequently, the drive can detect
oL1 [Motor Overload]
faults. If the drive detects
oL1
,
decrease the deceleration time or install a braking resistor to the drive.
•
The deceleration time during Overexcitation Deceleration changes when the motor characteristics and machine inertia change. Adjust the
n3-13 [OverexcitationBraking (OEB) Gain]
and
n3-23 [Overexcitation Braking Operation]
levels. Refer to
“
n3: HighSlip/
OverexciteBraking
”
for more information about the overexcitation function.
5 : Overexcitation/High Flux 2
Enables Overexcitation/High Flux 2. This function decreases the possible deceleration time more than Overexcitation/
High Flux.
The drive decreases motor speed and tries to keep the DC bus voltage at the
L3-17
level.
If the drive detects
oL1
, decrease the values set in
n3-13
and
n3-21
. If the drive detects
ov
, increase the values set in
C1-02, C1-04, C1-06, and C1-08 [Deceleration Times]
.
Note:
•
During Overexcitation/High Flux 2, the drive disables Hunting Prevention in V/f Control and also disables Speed Control that uses torque
limit in OLV Control.
•
Refer to
“
n3: HighSlip/OverexciteBraking
”
for more information about the overexcitation function.
■
L3-05: Stall Prevention during RUN
No.
(Hex.)
Name
Description
Default
(Range)
L3-05
(0493)
Stall Prevention during RUN
Sets the function to enable and disable Stall Prevention During Run.
2
(0 - Determined by A1-02)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...