778
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
■
E9-02: Maximum Speed
No.
(Hex.)
Name
Description
Default
(Range)
E9-02
(11E5)
Maximum Speed
Sets the maximum speed of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
Note:
The unit of measure changes when the setting of
o1-04 [V/f Pattern Display Unit]
.
EZ Tuning automatically sets this parameter to the value of [Motor Max Revolutions].
■
E9-03: Rated Speed
No.
(Hex.)
Name
Description
Default
(Range)
E9-03
(11E6)
Rated Speed
Sets the rated rotation speed of the motor.
Determined by E9-01
(100 - 7200 min
-1
)
EZ Tuning automatically sets this parameter to the value of [Rated Speed].
Note:
Set
E9-01 = 0 [Motor Type Selection = Induction (IM)]
before you set this parameter.
■
E9-04: Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E9-04
(11E7)
Base Frequency
Sets the rated frequency of the motor.
Determined by E9-01
(40.0 - 120.0 Hz)
Note:
The unit of measure changes when the setting of
o1-04 [V/f Pattern Display Unit]
.
EZ Tuning automatically sets this parameter to the value of [Base Frequency].
■
E9-05: Base Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E9-05
(11E8)
Motor Rated Voltage
Sets the rated voltage of the motor.
200 V Class: 230.0 V, 400 V:
460.0 V
(200 V Class: 0.0 - 255.0
V,400 V Class: 0.0 - 510.0
V)
EZ Tuning automatically sets this parameter to the value of [Base Voltage].
■
E9-06: Motor Rated Current (FLA)
No.
(Hex.)
Name
Description
Default
(Range)
E9-06
(11E9)
Motor Rated Current (FLA)
Sets the motor rated current in amps.
Determined by E9-01 and
o2-04
(10% to 200% of the drive
rated current)
Note:
When the drive model changes, the display units for this parameter also change.
•
0.01 A: models 2004 to 2042, 4002 to 4023
•
0.1 A: models 2056 to 2415, 4031 to 4720
The value set for
E9-06
becomes the reference value for motor protection. Enter the motor rated current shown on the
motor nameplate. Auto-Tuning the drive will automatically set
E9-06
to the value input for
“
Motor Rated Current
”
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...