760
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
Note:
Be aware of the following points when manually setting V/f patterns.
•
To set linear V/f characteristics at frequencies lower than
E1-06 [Base Frequency]
, set
E1-07 = E1-09 [Mid Point A Frequency = Minimum
Output Frequency]
. In this application, the drive ignores
E1-08 [Mid Point A Voltage]
.
•
Set the five frequencies as specified by these rules: Incorrect settings will cause
oPE10 [V/f Data Setting Error]
.
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 [Minimum Output Frequency ≤ Mid Point A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
•
Setting
E1-11 = 0 [Mid Point B Frequency = 0 Hz]
disables
E1-12 [Mid Point B Voltage]
. Ensure that the four frequencies are set
according to the following rules;
E1-09 ≤ E1-07 < E1-06 ≤ E1-04
•
When you use
A1-03 [Initialize]
to initialize the drive, it will not reset
E1-03
.
Figure 12.71 V/f Pattern
■
E1-01: Input AC Supply Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
200 V Class: 240 V, 400 V:
480 V
(200 V Class: 155 to 255 V,
400 V Class: 310 to 510 V)
NOTICE:
Set parameter E1-01 to align with the drive input voltage (not motor voltage). If this parameter is incorrect, the protective
functions of the drive will not operate correctly and it can cause damage to the drive.
Values Related to the Drive Input Voltage
The value set in
E1-01
is the base value that the drive uses for the motor protective functions in
. With a
400 V class drive, the detection level changes for some motor protective functions.
Table 12.42 Values Related to the Drive Input Voltage
Voltage
E1-01 Setting
Approximate Values
ov Detection Level
BTR Operation Level
(rr Detection Level)
L2-05
[Undervoltage
Detection Lvl (Uv1)]
L2-11
[KEB DC Bus
Voltage Setpoint]
L3-17
[DC Bus Regulation
Level]
200 V class
All settings
410 V
394 V
190 V
260 V
375 V
400 V class
Setting value ≥ 400 V
820 V
788 V
380 V
500 V
750 V
Setting value < 400 V
820 V
788 V
350 V
460 V
750 V
*1
This is the protection function enabled in drives with built-in braking transistors. These values show the level that will trigger the built-in
braking transistor. Refer to
“
YASKAWA AC Drive 72060001 Series Option Braking Unit and Braking Resistor Unit Installation Manual
(TOBPC72060001)
”
for more information.
■
E1-03: V/f Pattern Selection
No.
(Hex.)
Name
Description
Default
(Range)
E1-03
(0302)
V/f Pattern Selection
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you can make a
custom pattern.
F
(Determined by A1-02)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...