YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
715
•
L2-06
•
L2-07
When one of those parameters is set to a value between 600.1 s and 1000.0 s, you can set
C1-10 = 0
, but the time will
change to 600.00 s.
1 : 0.1 s (0.0 to 6000.0 s)
Sets acceleration and deceleration times in 0.1 s units. The setting range is 0.0 to 6000.0 s.
■
C1-11: Accel/Decel Time Switchover Freq
No.
(Hex.)
Name
Description
Default
(Range)
C1-11
(020A)
Accel/Decel Time Switching
Frequency
Sets the frequency at which the drive will automatically change acceleration and deceleration times.
Determined by A1-02
(0.0 - 590.0 Hz)
When output frequency get
C1-11
value, the drive automatically switches the acceleration and deceleration times. Set
this parameter to
0.0
to disable this function.
Figure 12.46 Accel/Decel Time Switching Frequency
lists the possible combinations of acceleration and deceleration time switchover frequencies and the
acceleration times for the Motor 2 Selection function.
Table 12.31 Motor and Acceleration and Deceleration Time Combination
C1-11
Motor 1
Motor 2
Acceleration Time
Deceleration Time
Acceleration Time
Deceleration Time
Less than the setting value
C1-07 [Acceleration Time 4]
C1-08 [Deceleration Time 4]
C1-07 [Acceleration Time 4]
C1-08 [Deceleration Time 4]
Equal to or more than the setting
value
C1-01 [Acceleration Time 1]
C1-02 [Deceleration Time 1]
C1-05 [Acceleration Time 3]
C1-06 [Deceleration Time 3]
■
C1-14: Accel/Decel Rate Frequency
No.
(Hex.)
Name
Description
Default
(Range)
C1-14
(0264)
RUN
Accel/Decel Rate Frequency
Sets the base frequency used to calculate acceleration and deceleration rates.
0.0 Hz
(0.0 - 590.0 Hz)
The acceleration and deceleration rates set in
C1-01 to C1-09 [Acceleration/Deceleration Times 1 to 4, Fast Stop
Time]
will change when the value of
C1-14
changes.
•
When
C1-14 = 0.0 Hz
–
C1-01, C1-03, C1-05, C1-07 [Acceleration Times 1 to 4]:
Time to accelerate from 0 Hz to
E1-04 [Maximum
Output Frequency]
–
C1-02, C1-04, C1-06, C1-08 [Deceleration Times 1 to 4], C1-09 [Fast Stop Time]:
Time to decelerate from
E1-
04
to 0 Hz.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...