YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
577
11.17 U: Monitors
◆
U1: Operation Status Monitors
No.
(Hex.)
Name
Description
MFAO Signal Level
U1-01
(0040)
Frequency reference
Shows the actual frequency reference value. Parameter
o1-03 [Keypad Display Unit Selection]
sets
the display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(-10 V to +10 V)
U1-02
(0041)
Output Frequency
Shows the actual output frequency. Parameter
o1-03 [Keypad Display Unit Selection]
sets the display
units.
Unit: 0.01 Hz
10 V = Maximum frequency
(-10 V to +10 V)
U1-03
(0042)
Output Current
Shows the actual output current.
The keypad shows the value of
U1-03
in amperes (A). When looking at the monitor through
MEMOBUS/Modbus communications, the current is
“
8192 = drive rated current (A).
”
Calculate the
current from the monitor value that is in at MEMOBUS/Modbus communications using
“
Numerals
being displayed / 8192 × drive rated current (A).
”
Unit: Determined by the drive model.
•
0.01 A: 2004 to 2042, 4002 to 4023
•
0.1 A: 2056 to 2415, 4031 to 4720
10 V = Drive rated current
U1-04
(0043)
Control Method
Shows the drive control method.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
4 : Advanced Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
7 : PM Closed Loop Vector
8 : EZ Vector Control
No signal output available
U1-05
(0044)
Motor Speed
Shows the actual detected motor speed. Parameter
o1-03 [Keypad Display Unit Selection]
sets the
display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(-10 V to +10 V)
U1-06
(0045)
Output Voltage Ref
Shows the output voltage reference.
Unit: 0.1 V
200 V class: 10 V = 200
Vrms
400 V class: 10 V = 400
Vrms
U1-07
(0046)
DC Bus Voltage
Shows the DC bus voltage.
Unit: 1 V
200 V class: 10 V = 400 V
400 V class: 10 V = 800 V
U1-08
(0047)
Output Power
Shows the internally-calculated output power.
Changing the setting of
A1-02 [Control Method Selection]
also changes the signal level of the analog
output.
•
A1-02 = 0, 1: Drive capacity (kW)
•
A1-02 = 2, 3, 4:
Motor Rated Power [E2-11]
(kW)
•
A1-02 = 5, 6, 7:
PM Motor Rated Power [E5-02]
(kW)
•
A1-02 = 8:
Motor Rated Power [E9-07]
(kW)
Unit: The display units are different for different models:
•
0.01 kW: 2004 to 2042, 4002 to 4023
•
0.1 kW: 2056 to 2415, 4031 to 4720
10 V: Drive capacity (motor
rated power) kW
(-10 V to +10 V)
U1-09
(0048)
Torque Reference
Shows the internal torque reference value.
Unit: 0.1%
10 V = Motor rated torque
(-10 V to +10 V)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...