Code
Name
Causes
Possible Solutions
oH
Heatsink Overheat
The ambient temperature is high and the heatsink
temperature is more than the
L8-02 [Overheat Alarm
Level]
.
•
Measure the ambient temperature.
•
Increase the airflow around the drive.
•
Install a cooling device (cooling fan or air conditioner) to lower
the ambient temperature.
•
Remove objects near the drive that are producing too much heat.
There is not sufficient airflow around the drive.
•
Give the drive the correct installation space as shown in the
manual.
•
Make sure that there is sufficient circulation around the control
panel.
•
Examine the drive for dust or other unwanted materials that
could clog the cooling fan.
•
Remove unwanted materials that prevent air circulation.
The internal cooling fan or fans have stopped.
1.
Use the procedures in this manual to replace the cooling fan.
2.
Set
o4-03 = 0 [Fan Operation Time Setting = 0 h]
to reset the
cooling fan operation time.
Note:
•
The drive detects this error if the heatsink temperature of the drive is more than
L8-02
.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
•
Set the stopping method for this fault in
L8-03 [Overheat Pre-Alarm Selection]
.
Code
Name
Causes
Possible Solutions
oH2
External Overheat (H1-XX=B)
An external device sent an
oH2
.
1.
Find the external device that output the overheat alarm.
2.
Remove the cause of the problem.
3.
Clear the
Overheat Alarm (oH2) [H1-xx = B]
that was set to
MFDI terminals S1 to S8.
Note:
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
Code
Name
Causes
Possible Solutions
oH3
Motor Overheat (PTC Input)
The thermistor wiring that detects motor temperature
is defective.
Correct wiring errors.
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault
The motor has overheated.
•
Check the load level, acceleration/deceleration time, and motor
start/stop frequency (cycle time).
•
Decrease the load.
•
Increase the values set in
C1-01 to C1-08 [Acceleration/
Deceleration Times]
.
•
Set
E2-01 [Motor Rated Current (FLA)]
correctly to the value
specified by the motor nameplate.
•
Make sure that the motor cooling system is operating correctly,
and repair or replace it if it is damaged.
•
Adjust
E1-04 to E1-10 [V/f Pattern Parameters]
. For motor 2,
adjust
E3-04 to E3-10
. Decrease the values set in
E1-08 [Mid
Point A Voltage]
and
E1-10 [Minimum Output Voltage]
.
Note:
If the values set in
E1-08
and
E1-10
are too low, the overload
tolerance will decrease at low speeds.
Note:
•
When
H3-02, H3-10, or H3-06 = E [MFAI Function Select = Motor Temperature (PTC Input)]
, the drive detects this fault if the motor overheat signal entered to analog input
terminals A1 to A3 is more than the alarm detection level.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
L1-03 [Motor Thermistor oH Alarm Select]
.
Code
Name
Causes
Possible Solutions
oL3
Overtorque 1
A fault occurred on the machine.
Example: The machine is locked.
Examine the machine and remove the cause of the fault.
The parameters are incorrect for the load.
Adjust
L6-02 [Torque Detection Level 1]
and
L6-03 [Torque
Detection Time 1]
settings.
Note:
•
The drive detects this fault if the drive output current is more than the level set in
L6-02
for longer than
L6-03
.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 10 [MFDO Function Select = Alarm]
will be ON.
•
Set the conditions that trigger the minor fault using
L6-01 [Torque Detection Selection 1]
.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...