1.3 Features and Advantages of Control Methods
26
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
1.3
Features and Advantages of Control Methods
This drive has 9 available control methods from which to select for different applications.
,
, and
give information about the features of each control method.
Table 1.4 V/f and CL-V/f Features and Advantages of Control Methods
Control method selection
V/f Control
(V/f)
V/f Control with Encoder
(CL-V/f)
Notes
Controlled Motor
Induction Motor
-
Parameter Setting
A1-02 = 0
A1-02 = 1
-
Basic Control
V/f
Closed loop V/f control with speed
correction
-
Main Applications
General-purpose variable speed control to
connect more than one motor to one drive.
High-precision speed control with encoders
on machines
-
PG Option Card
Not necessary
Necessary (PG-B3 or PG-X3)
-
Maximum Output Frequency
590 Hz
400 Hz
-
Speed Control Range
1:40
1:40
This is the range of variable control.
When you connect and operate motors in this mode,
think about the increase in motor temperature.
Starting Torque
150% / 3 Hz
150% / 3 Hz
This is the motor torque that the drive can supply at low
speed during start-up and the related output frequency
(rotation speed).
You must think about drive capacity and motor capacity
when a large quantity of torque is necessary at low
speed.
Auto-Tuning
Rotational and Line-to-Line Resistance
(usually not necessary)
Rotational and Line-to-Line Resistance
(usually not necessary)
Automatically tunes electrical motor parameters.
Torque Limits
No
No
Controls maximum motor torque to prevent damage to
machines and loads.
Torque Control
No
No
Directly controls motor torque to control tension and
other parameters.
Droop Control
No
No
Sets load torque slip for motors. Distributes motor loads.
Zero Servo Control
No
No
Locks servos without an external position controller to
prevent movement caused by external force.
Speed Search
Yes
-
Immediately estimates (or detects) motor speed and
direction when coasting to a stop to quickly start-up the
drive without stopping the motor.
Automatic Energy-saving
Control
Yes
Yes
Automatically adjusts the voltage applied to motors to
maximize motor efficiency for all load sizes.
High Slip Braking (HSB)
Yes
Yes
Increases motor loss to let the motor decelerate faster
than usual without a braking resistor. Motor
characteristics have an effect on this function.
Feed Forward Control
No
No
Compensates effects of the system inertia to increase the
speed precision when the load changes.
KEB Ride-Thru Function
Yes
Yes
Quickly and safely stops the motor during power loss
and automatically starts operation at the previous speed
when restores power without coasting the motor.
Overexcitation Deceleration
Yes
Yes
Sets the V/f higher than the setting value during
deceleration to increase motor loss and decrease
deceleration time.
Overvoltage Suppression
Function
Yes
Yes
Adjusts speed during regeneration to prevent
overvoltage.
*1
Note these points when you use this function:
•
When you can decouple the motor and machine for a test run, use Rotational Auto-Tuning. You must make adjustments to the control
in the range where there is no vibration in the machine after Rotational Auto-Tuning.
•
Motor loss increases during overexcitation braking and high-slip braking. Use a maximum braking frequency of 5% ED and a
maximum braking time of 90 seconds. After you start high-slip braking, you cannot restart the motor until it stops. Use overexcitation
braking to decelerate over a shorter time at a pre-determined speed.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 30: ...1 3 Features and Advantages of Control Methods 30 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 144: ...4 4 Start up Procedures 144 YASKAWA SIEPC71061737B GA800 Drive Technical Reference Figure 4 8 Basic Steps before Startup...
Страница 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 370: ...7 10 Troubleshooting Without Fault Display 370 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Страница 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...