YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
505
•
If too much current flows during acceleration, decrease the setting value.
Note:
When
A1-02 = 8 [Control Method Selection = EZOLV]
, this parameter will always be in effect for speed ranges less than
n7-10 [Pull-in
Current Switching Speed]
.
■
n8-52: ACR P Gain
No.
(Hex.)
Name
Description
Default
(Range)
n8-52
(053F)
Expert
ACR P Gain
Sets the proportional gain of the current regulator. Usually it is not necessary to change this setting.
10.0
(-100.0 - 100.0)
■
n8-54: Voltage Error Compensation Time
No.
(Hex.)
Name
Description
Default
(Range)
n8-54
(056D)
Expert
Voltage Error Compensation
Time
Sets the time constant that the drive uses when adjusting for voltage errors.
1.00 s
(0.00 - 10.00 s)
Adjust this parameter in these conditions:
•
If oscillation occurs at the time of start up, increase the setting value.
•
If hunting occurs when operating at low speed, increase the setting value.
•
If fast changes in the load cause hunting, increase the setting value in 0.1-unit increments. If you cannot stop
hunting, set
n8-51 [Pull-in Current @ Acceleration]
to 0% and set
n8-54
to 0.00 s, and disable compensation for
voltage errors.
■
n8-55: Motor to Load Inertia Ratio
No.
(Hex.)
Name
Description
Default
(Range)
n8-55
(056E)
Motor to Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
0
(0 - 3)
Adjust in the following situations.
•
If torque and speed response is unsatisfactory, gradually increase the setting from 0.
•
If the motor does not run smoothly, gradually increase the setting from 0.
•
If the motor stalls during run at constant speed, gradually increase the setting from 0.
•
If there is vibration or hunting, decrease the setting.
Note:
•
If the value is set too low, the drive will detect
STPo [Motor Step-Out Detected]
.
•
If you use one motor or more than motor at low inertia and the value is too high, there can be vibration in the motor.
0 : Below 1:10
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is less than 1:10
•
There are large current ripples
1 : Between 1:10 and 1:30
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is approximately 1:10 to 1:30
•
Parameter
n8-55 = 0
and the drive detects
STPo
because of an impact load or sudden acceleration/deceleration.
2 : Between 1:30 and 1:50
Use this setting in these conditions:
•
The ratio between the motor inertia and machine inertia is approximately 1:30 to 1:50
•
Parameter
n8-55 = 1
and the drive detects
STPo
because of an impact load or sudden acceleration/deceleration.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV