L7-36: Regen Torque Limit Derate Freq
No.
(Hex.)
Name
Description
Default
(Range)
L7-36
(1B58)
Expert
Regen Torque Limit Derate
Freq
Sets the frequency width at which
L7-35 [Low Freq Regen Torque Limit Lvl]
operates.
6.0 Hz
(0.0 - 30.0 Hz)
If the drive detects
oC [Overcurrent]
faults when you connect regenerative loads at low speed, increase the setting
value. Decreases the torque limit as specified by the setting of
L7-35
in a range of 0 ≤ output frequency <
L7-36
.
When the torque limit gradually changes as specified by the output frequency until the output frequency =
L7-36
, the
value changes to the setting of
L7-03 [Forward Regenerative Trq Limit]
and
L7-04 [Reverse Regenerative Trq Limit]
.
Note:
If you increase the setting of
L7-36
, the motor will rotate at a speed higher than specified when a you input a regenerative load. Do not set
the value higher than necessary.
◆
L8: Drive Protection
L8 parameters
set protective functions that prevent faults such as overheating, phase loss, and ground faults.
■
L8-01: 3% ERF DB Resistor Protection
No.
(Hex.)
Name
Description
Default
(Range)
L8-01
(04AD)
3% ERF DB Resistor
Protection
Sets the function to enable braking resistor protection with a Yaskawa ERF series braking resistor
(3% ED) installed on the heatsink.
0
(0, 1)
0 : Disabled
Disables braking resistor protection. Use this setting for dynamic braking options that are not Yaskawa ERF series
braking resistors.
1 : Enabled
Enables protection for Yaskawa ERF series braking resistors.
Note:
Set
L8-01 = 1
and
H2-01 to H2-03 = D [MFDO Function Select = Braking Resistor Fault]
. Use a sequence to turn OFF power with MFDO.
■
L8-02: Overheat Alarm Level
No.
(Hex.)
Name
Description
Default
(Range)
L8-02
(04AE)
Overheat Alarm Level
Sets the
oH
detection level in temperature.
Determined by o2-04, C6-01
(50 - 150 °C)
If the heatsink temperature is more than the temperature set in this parameter, the drive detects an overheat pre-alarm.
To enable this function, set one of
H2-01
to
H2-03 [MFDO Function Select]
to
20 [Drive Overheat Pre-Alarm (oH)]
.
If the temperature increases to the overheat fault level, the drive will trigger an
oH1 [Heatsink Overheat]
fault and
stop operation.
■
L8-03: Overheat Pre-Alarm Selection
No.
(Hex.)
Name
Description
Default
(Range)
L8-03
(04AF)
Overheat Pre-Alarm
Selection
Sets the operation of drives when an
oH
alarm is detected.
3
(0 - 4)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-
MC turns OFF.
1 : Coast to Stop
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM