414
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
■
3: Auxiliary Frequency Reference 2
Setting Value
Function
Description
3
Auxiliary Frequency
Reference 2
Sets Reference 3 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference 2) from the
analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is a setting value of 100%.
■
4: Output Voltage Bias
Setting Value
Function
Description
4
Output Voltage Bias
Set this parameter to input a bias signal and amplify the output voltage.
The gain (%) for the MFAI terminals A1, A2, and A3 is 100% of the voltage class standard, which is 200 V for 200 V
class drives and 400 V for 400 V class drives. The bias (%) for MFAI terminals A1, A2, and A3 is 100% of the
voltage configured for
E1-05 [Maximum Output Voltage]
.
Note:
The gain for each terminal A1, A2, and A3 is configured independently with
H3-03 [Terminal A1 Gain Setting], H3-11 [Terminal A2 Gain
Setting], and H3-07 [Terminal A3 Gain Setting]
. The bias for each terminal A1, A2, and A3 is configured independently with
H3-04
[Terminal A1 Bias Setting], H3-12 [Terminal A2 Bias Setting], and H3-08 [Terminal A3 Bias Setting]
.
Figure 2.104 Output Voltage Bias through Analog Input
■
5: Accel/Decel Time Gain
Setting Value
Function
Description
5
Accel/Decel Time Gain
Enters a signal to adjust the gain used for
C1-01 to C1-08 [Acceleration/Deceleration Times 1 to 4]
and
C1-09 [Fast Stop Time]
when the full scale analog signal (10 V or 20 mA) is 100%.
When you enable
C1-01 [Acceleration Time 1]
, the acceleration time is:
Acceleration Time 1 = Setting value of
C1-01
× acceleration and deceleration time gain / 100
Figure 2.105 Acceleration/Deceleration Time Gain through Analog Input
■
6: DC Injection Braking Current
Setting Value
Function
Description
6
DC Injection Braking
Current
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...