YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
397
OFF : The output frequency is higher than the value of
L4-03
+
L4-04
.
Figure 2.97 Example of Frequency Detection 3 (value of L4-03 Is Positive)
Note:
shows the time chart when
L4-07 = 1 [Speed Agree Detection Selection = Detection Always Enabled]
. The default setting of
L4-
07
is
0 [No detection during baseblock]
. When the speed agreement detection selection is
“
No Detection during Baseblock
”
, the terminal is
deactivated when the drive output stops.
■
16: Frequency Detection 4
Setting Value
Function
Description
16
Frequency Detection 4
The terminal activates when the output frequency is higher than the value of
L4-03 [Speed Agree Detection Level (+/-)]
. After the
terminal activates, the terminal stays on until the output frequency is at the value of
L4-03
-
L4-04
.
Note:
•
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
•
The drive outputs the motor speed status if
A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]
.
ON : The output frequency is higher than the value of
L4-03
.
OFF : The output frequency is less than the value of “
L4-03
-
L4-04
”, or it is not higher than the value
of
L4-03
.
Figure 2.98 Example of Frequency Detection 4 (value of L4-03 Is Positive)
■
17: Torque Detection 1 (N.C.)
Setting Value
Function
Description
17
Torque Detection 1 (N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the
L6 [Torque Detection]
parameters to set torque detection.
OFF : The output current/torque is more than the torque value set with
L6-02 [Torque Detection
Level 1]
, or the level is less than the torque value set with
L6-02
for longer than the time set with
L6-
03 [Torque Detection Time 1]
.
Note:
•
When
L6-01 ≥ 5
, the drive will detect when the output current/torque is less than the detection level of
L6-02
for longer than the time set in
L6-03
.
•
Refer to
“
L6: Torque Detection
”
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV