Figure 2.95 Speed Agree 2 Time Chart
■
14: User-Set Speed Agree 2
Setting Value
Function
Description
14
User-Set Speed Agree 2
The terminal activates when the output frequency is in the range of
L4-03 [Speed Agree Detection Level (+/-)]
±
L4-04 [Speed
Agree Detection Width (+/-)]
and in the range of the frequency reference ±
L4-04
.
Note:
•
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]
.
ON : The output frequency is in the range of “
L4-03
±
L4-04
” and the range of frequency reference
±
L4-04
.
OFF : The output frequency is not in the range of “
L4-03
±
L4-04
” or the range of frequency
reference
±
L4-04
.
Figure 2.96 Example of User-set Speed Agree 2 (L4-03 Is Positive)
■
15: Frequency Detection 3
Setting Value
Function
Description
15
Frequency Detection 3
The terminal deactivates when the output frequency is higher than the value of
“
L4-03 [Speed Agree Detection Level (+/-)]
+
L4-04
[Speed Agree Detection Width (+/-)]
”
. After the terminal deactivates, the terminal stays off until the output frequency is at the value
of
L4-03
.
Note:
•
The detection level set in
L4-03
is a signed value. The drive will only detect in one direction.
•
The drive outputs the motor speed status when
A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]
.
ON : The output frequency is less than the value of
L4-03
or is not higher than the value of
L4-03
+
L4-04
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV