376
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Note:
•
If you set
KEB Ride-Thru 1 [H1-xx = 65, 66]
and
KEB Ride-Thru 2 [H1-xx = 7A, 7B]
at the same time, the drive will detect
oPE03 [Multi-
Function Input Setting Err]
.
•
Refer to
“
KEB Ride-Thru function
”
for more information.
■
66: KEB Ride-Thru 1 Activate (N.O.)
Setting Value
Function
Description
66
KEB Ride-Thru 1 Activate
(N.O.)
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
ON : Deceleration during momentary power loss
OFF : Normal operation
When you enable KEB Ride-Thru 1, set
L2-29 [KEB Method Selection]
. The drive operates with the selected KEB
method.
Note:
•
If you set
KEB Ride-Thru 1 [H1-xx = 65, 66]
and
KEB Ride-Thru 2 [H1-xx = 7A, 7B]
at the same time, the drive will detect
oPE03 [Multi-
Function Input Setting Err]
.
•
Refer to "KEB Ride-Thru function" for more information.
■
67: Communications Test Mode
Setting Value
Function
Description
67
Communications Test Mode
Set the function for the drive to self-test RS-485 serial communications operation.
The Self-Diagnostics function connects the transmission terminal of the control terminal block to the reception
terminal. The function transmits the data that the drive sent to make sure that the drive can communicate correctly.
Note:
Refer to MEMOBUS/Modbus communications
“
Self-Diagnostics
”
for the self-diagnostics procedure.
■
68: High Slip Braking (HSB) Activate
Setting Value
Function
Description
68
High Slip Braking
Sets the command to use high-slip braking to stop the motor.
Note:
•
When you restart the drive after you use high-slip braking, make sure that the drive fully stops the motor then clear the high-slip braking
input.
•
Refer to
“
n3: High Slip/Overex Braking
”
for more information.
■
6A: Drive Enable
Setting Value
Function
Description
6A
Drive Enable
Sets the function to show
dnE [Drive Enabled]
on the keypad and ignore Run commands when the terminal is OFF.
If you input the Run command before you turn ON the Drive Enable terminal, you must input the Run command
again to operate the drive. When the terminal set for Drive Enable is turned OFF when the drive is operating, the
drive will use the stopping method set in
b1-03 [Stopping Method Selection]
to stop the motor.
ON : Run command is accepted.
OFF : Run command is disabled. When the drive is running, it stops according to
b1-03
setting.
■
71: Torque Control
Setting Value
Function
Description
71
Torque Control
Sets the function to switch between torque control and speed control.
ON : Torque control
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 14: ...i 2 Using the Product Safely 14 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...
Страница 172: ...1 22 Parameters Changed by PM Motor Code Selection 172 YASKAWA TOEPYAIGA8002B GA800 Drive Programming...