348
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
■
F6-53: DeviceNet PPA Setting
No.
(Hex.)
Name
Description
Default
(Range)
F6-53
(03C4)
DeviceNet PPA Setting
Sets the format of data that the drive sends to the DeviceNet communication master.
71
(0 - 255)
Note:
If
F6-52 [DeviceNet PCA Setting]
and
F6-53 [DeviceNet PPA Setting]
are not correct, the value is reset to default.
■
F6-54: DeviceNet Idle Fault Detection
No.
(Hex.)
Name
Description
Default
(Range)
F6-54
(03C5)
DeviceNet Idle Fault
Detection
Sets the function to detect
EF0 [Option Card External Fault]
when the drive does not receive data
from the DeviceNet master.
0
(0 - 4)
0 : Enabled
1 : Disabled, No Fault Detection
Does not detect
EF0
issues.
2 : Vendor Specific
3 : RUN Forward
4 : RUN Reverse
■
F6-55: DeviceNet Baud Rate Monitor
No.
(Hex.)
Name
Description
Default
(Range)
F6-55
(03C6)
DeviceNet Baud Rate
Monitor
Sets the function to see the actual DeviceNet communications speed using the keypad. This
parameter functions as a monitor only.
0
(0 - 2)
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
■
F6-56: DeviceNet Speed Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-56
(03D7)
DeviceNet Speed Scaling
Sets the speed scale for DeviceNet communication.
0
(-15 - +15)
■
F6-57: DeviceNet Current Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-57
(03D8)
DeviceNet Current Scaling
Sets the current scale of the DeviceNet communication master.
0
(-15 - +15)
■
F6-58: DeviceNet Torque Scaling
No.
(Hex.)
Name
Description
Default
(Range)
F6-58
(03D9)
DeviceNet Torque Scaling
Sets the torque scale of the DeviceNet communication master.
0
(-15 - +15)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV