276
YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
Related Parameters
Multi-Step Speed
Reference 1
H1-xx = 3
Multi-Step Speed
Reference 2
H1-xx = 4
Multi-Step Speed
Reference 3
H1-xx = 5
Multi-Step Speed
Reference 4
H1-xx = 32
Jog Reference
H1-xx = 6
Reference 11 (
d1-11
)
OFF
ON
OFF
ON
OFF
Reference 12 (
d1-12
)
ON
ON
OFF
ON
OFF
Reference 13 (
d1-13
)
OFF
OFF
ON
ON
OFF
Reference 14 (
d1-14
)
ON
OFF
ON
ON
OFF
Reference 15 (
d1-15
)
OFF
ON
ON
ON
OFF
Reference 16 (
d1-16
)
ON
ON
ON
ON
OFF
Jog Reference (
d1-17
)
-
-
-
-
ON
*1
The Jog Frequency Reference (JOG command) overrides all other frequency references.
Figure 2.60 Time Chart for Multi-step Speed Reference/JOG Reference
■
d1-01: Reference 1
No.
(Hex.)
Name
Description
Default
(Range)
d1-01
(0280)
RUN
Reference 1
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection
.
0.00 Hz
(0.00 - 590.00 Hz)
Note:
•
The upper limit value changes when the
E1-04 [Maximum Output Frequency]
and
d2-01 [Frequency Reference Upper Limit]
values
change. Calculate the upper limit value with this formula:
Upper limit value = (
E1-04
) × (
d2-01
) / 100
•
When
A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM]
, the drive changes
o1-03 = 1 [0.01% (100% = E1-04)]
.
•
To set
d1-01
to 1-step speed parameter in a multi-step speed operation, set
b1-01 = 0 [Frequency Reference Selection 1 = Keypad]
.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM
EZOLV