7.4 Model-Specific Specifications (400 V Class)
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
515
Model
Duty Rating
4031
4038
4044
4060
4075
4089
4103
Power Supply
Input Power
(kVA) at 380 V
Input
HD
24
33
40
34
46
57
69
ND
33
40
48
46
57
69
84
Input Power
(kVA) at 460 V
Input
HD
21
28
35
30
40
49
59
ND
28
35
41
40
49
59
72
*1
The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output complies with 460 V motor ratings as specified in NEC Table 430.250. The rated output current of
the drive output amps must be equal to or more than the motor rated current.
Table 7.7 Rating (400 V Class)
Model
Duty Rating
4140
4168
4208
4250
4302
4371
4414
Maximum Applicable Motor
Output (kW) at 380 V Input
HD
55
75
90
110
132
160
200
ND
75
90
110
132
160
200
220
The maximum applicable motor
output (HP) at 460 V Input
HD
75
100
125
150
200
250
300
ND
100
125
150
200
250
300
350
Input
Rated Input
Current (A) at
380 V Input
HD (AC)
105
142
170
207
248
300
373
HD (DC)
129
174
209
254
304
367
457
ND (AC)
142
170
207
248
300
373
410
ND (DC)
174
209
254
304
367
457
502
Rated Input
Current (A) at
460 V Input
HD (AC)
86.9
118
141
171
232
289
346
HD (DC)
106.0
144
172
210
284
354
424
ND (AC)
118
141
171
232
289
346
403
ND (DC)
144
172
210
284
354
424
494
Output
Rated Output
Current (A)
HD
112
150
180
216
260
304
371
ND
140
168
208
250
302
371
414
Power Supply
Input Power
(kVA) at 380 V
Input
HD
84
113
135
165
198
239
297
ND
113
135
165
198
239
297
327
Input Power
(kVA) at 460 V
Input
HD
72
98
117
142
193
240
288
ND
98
117
142
193
240
288
335
*1
The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output complies with 460 V motor ratings as specified in NEC Table 430.250. The rated output current of
the drive output amps must be equal to or more than the motor rated current.
Table 7.8 Rating (400 V Class)
Model
Input Voltage
Duty Rating
4477
4568
4605
4720
Maximum Applicable Motor Output (kW)
< 460 V
HD
220
250
315
315
ND
250
315
355
370
≥ 460 V
HD
260
300
335
370
ND
300
335
370
450
Maximum Applicable Motor Output (HP)
< 460 V
HD
300
335
400
400
ND
335
400
450
500
≥ 460 V
HD
350
400
450
500
ND
400
450
500
600
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...