6.10 Fine Tuning during Test Runs (Adjust the Control Function)
YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
505
Issue
Parameter Number
Possible Solutions
Default
Recommended Setting
Stalling or oscillation occurs when
you apply the load during constant
speed
n8-47 [Pull-in Current Comp Filter
Time]
Decrease the setting value in
increments of 0.2 s.
5.0 s
-
n8-48 [Pull-in/Light Load Id
Current]
Increase the setting value in
increments of 5%.
30%
-
n8-55 [Motor to Load Inertia
Ratio]
Increase the setting value.
Note:
When you operate a single
motor or with a minimum
quantity of inertia, if you set
this value too high, it can cause
motor oscillation.
0
Near the load inertia ratio.
Hunting or oscillation
n8-45 [Speed Feedback Detection
Gain]
Increase the setting value in
increments of 0.05.
0.80
-
The drive detects
STPo [Motor
Step-Out Detected]
fault when the
load is not too high.
•
E5-09 [PM Back-EMF Vpeak
(mV/(rad/s))]
•
E5-24 [PM Back-EMF L-L
Vrms (mV/rpm)]
•
Adjust the setting value.
•
Examine the motor code on the
motor nameplate or the data
sheet, then set correct values for
E5-09
or
E5-24
.
•
Yaskawa motor
Set the motor code from the
motor nameplate.
•
Motor from another
manufacturer
Set the values from the test
report.
The drive detected stalling or
STPo
[Motor Step-Out Detected]
at high
speed and maximum output
voltage.
n8-62 [Output Voltage Limit
Level]
Set to a value lower than the actual
input voltage.
•
200.0 V
•
400.0 V
-
*1
The default setting changes when the settings for
E5-01 [Motor Code Selection]
and
o2-04 [Drive Model (KVA) Selection]
change.
◆
Advanced Open Loop Vector Control Method for PM Motors
Table 6.22 Parameters for Fine Tuning the Drive (
A1-02 = 6 [AOLV/PM]
)
Issue
Parameter Number
Possible Solutions
Default
Recommended Setting
•
Unsatisfactory motor torque
and speed response
•
Hunting or oscillation
•
High speed
C5-01 [ASR Proportional Gain
1]
•
Low speed
C5-03 [ASR Proportional Gain
2]
•
If torque or speed response are
slow, increase the setting value
in increments of 5.00.
•
If hunting or oscillation occur,
decrease the setting value.
10.00
5.00 to 30.00
•
High speed
C5-02 [ASR Integral Time 1]
•
Low speed
C5-04 [ASR Integral Time 2]
•
If torque or speed response are
slow, decrease the setting value.
•
If hunting or oscillation occur,
increase the setting value.
0.500 s
0.300 s to 1.000 s
The drive cannot find ASR
proportional gain or integral time
for low speed or high speed.
C5-07 [ASR Gain Switchover
Frequency]
Change the ASR proportional gain
and ASR integral time to conform
to the output frequency.
0.0%
0.0% to maximum rotation speed
Hunting or oscillation
C5-06 [ASR Delay Time]
If the rigidity of the machine is
unsatisfactory and vibration is
possible, increase the setting value
in increments of 0.010.
0.016 s
0.016 s to 0.035 s
Step-out
E1-xx parameters, E5-xx
parameters
Refer to the motor nameplate or
test report and set
E1-xx
or
E5-xx
correctly.
-
-
*1
The best values for a no-load operation are different than the best values for actual loading operation.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...