YASKAWA
TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
375
A - Main circuit power supply
B - Branch circuit protection
C - 6-Phase/12-Pulse isolation transformer
D - Fuse
E - Dynamic braking resistor (option)
F - CDBR dynamic braking unit (option)
G - Motor
Figure 5.30 Standard 12-Pulse Input Main Circuit Terminal Connections
*1
Refer to
Short Circuit Protection Requirements for UL Listing on page 419
for fuses for the secondary side of the 6-Phase/12-Pulse
transformer.
*2
Refer to local codes for correct branch circuit protection (BCP) on the primary side of the 6-Phase/12-Pulse transformer.
*3
You can install a dynamic braking resistor to terminals - and +3 on models Txxx.
*4
You can install a CDBR dynamic braking unit to models Txxx.
A - Branch circuit protection
B - Input reactor (optional)
C - Fuse
D - Delta to Wye transformer
E - Balancing reactor
F - Braking resistor (optional)
G - CDBR braking unit (optional)
H - Motor
Figure 5.31 Hybrid 12-Pulse Main Circuit terminal Connections
■
Input Phase Loss Detection
NOTICE:
Damage to Equipment. Set L8-05 = 4 [Input Phase Loss Protection Sel = Enabled] to detect input phase loss. If L8-05
≠
4,
it can cause damage to the drive main circuit from input phase loss.
Содержание GA800 Series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 430: ...5 18 Motor Application Precautions 430 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Страница 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...