368
YASKAWA
TOEPYAIGA5002A GA500 Programming
Figure 2.112 KEB Function Wiring Example
■
Parameters for KEB Ride-Thru
shows the parameters that adjust the KEB Ride-Thru function. Parameter settings are different for the
different KEB methods set in
L2-29 [Kinetic Energy Backup Method]
.
Table 2.61 Parameters for KEB Ride-Thru
No.
Name
Configuring Settings
L2-29 [Kinetic Energy Backup Method]
0
1
2
3
C1-09
Fast Stop Time
•
If
ov [Overvoltage]
occurs during KEB deceleration, increase the setting value.
•
If
Uv1 [DC Bus Undervoltage]
occurs during KEB deceleration, decrease the
setting value.
-
-
-
C2-03
S-Curve Time @ Start of Decel
•
If
ov
occurs immediately after you start KEB deceleration, increase the setting
value.
•
If
Uv1
occurs immediately after you start KEB deceleration, decrease the setting
value.
x
-
x
x
L2-05
Undervoltage Detection Lvl
(Uv1)
If
Uv1
occurs immediately after you start KEB deceleration, increase the setting
value to detect power loss more quickly.
x
x
x
x
L2-06
Does KEB Tuning.
•
Kinetic Energy Backup Decel Time
•
If
ov
or
Uv1
occur during KEB deceleration after KEB Tuning, set
L2-06
in these
conditions:
–
If
ov
occurs, increase the setting value
–
If
Uv1
occurs, decrease the setting value.
-
-
x
L2-07
Kinetic Energy Backup Accel
Time
Sets the acceleration time to return to the frequency reference value before a power
loss, after you cancel the KEB operation. When
L2-07 = 0
, the drive uses the
standard acceleration times set in
C1-01, C1-03, C1-05, and C1-07 [Acceleration
Time]
.
x
x
x
x
L2-08
Frequency Gain at KEB Start
•
If
ov
occurs immediately after you start operation, decrease the setting value.
•
If
Uv1
occurs immediately after you start operation, increase the setting value.
x
-
x
x
L2-10
Minimum KEB Time
•
With KEB Ride-Thru
There is
Uv1
because you set a digital input for KEB Ride-Thru and the device
that controls the input operated too slowly after power loss.
•
Without KEB Ride-Thru
If the DC bus voltage overshoots immediately after KEB Ride-Thru starts,
increase L2-10 to longer than the overshoot.
x
x
x
x
L2-11
KEB DC Bus Voltage Setpoint
•
Single Drive KEB Ride-Thru 2
Set to approximately 1.22 x input voltage.
•
Single Drive KEB Ride-Thru 1, System KEB Ride-Thru 1, or System KEB Ride-
Thru 2
Set to approximately 1.4 x input voltage.
x
x
x
x
L3-20
DC Bus Voltage Adjustment
Gain
•
If
ov
or
Uv1
occurs at the start of deceleration when you use KEB operation,
increase this value in 0.1-unit increments.
•
If there is torque ripple during deceleration when you use KEB Ride-Thru,
decrease the value.
-
x
-
-
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...