2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
331
■
67: Comparator2
Setting Value
Function
Description
67
Comparator2
The terminal activates if the monitor value set with
H2-26 [Comparator 2 Monitor Selection]
is not in the range of the values of
H2-
27 [Comparator 2 Lower Limit]
and
H2-28 [Comparator 2 Upper Limit]
for the time set in
H2-30 [Comparator 2 On-Delay Time]
.
A - H2-30
[Comparator 2 On-Delay Time]
B - H2-31
[Comparator 2 Off-Delay Time]
Figure 2.86 Comparator 2 Output Time Chart
Note:
The drive compares the monitors set with
H2-26
as absolute values.
■
69: External Power 24V Supply
Setting Value
Function
Description
69
External Power 24V Supply
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
■
6A: Data Logger Error
Setting Value
Function
Description
6A
Data Logger Error
The terminal activates when the drive detects
LoG [Com Error / Abnormal SD card]
.
■
90 to 92: DWEZ Digital Output 1 to 3
Setting Value
Function
Description
90 - 92
DWEZ Digital Output 1 to 3
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
■
100 to 192: Inverse output of 0 to 92
Setting Value
Function
Description
100 - 192
Inverse output of 0 to 92
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to inversely
output.
For example, set
H2-xx = 10E
for the inverse output of
E [Fault]
.
◆
H3: Analog Inputs
WARNING!
Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...