2.8 H: Terminal Function Selection
YASKAWA
TOEPYAIGA5002A GA500 Programming
313
■
H2-09: Modbus Register 2 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-09
(0B3C)
Modbus Register 2 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets the address of the register that is output to
Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63]
and uses the bit
in
H2-10 [Modbus Register 2 Bit Select]
.
■
H2-10: Modbus Register 2 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets the bit of the register that is output to
Modbus Reg 2 Status Satisfied [H2-01 to H2-03 = 63]
and uses the address
in
H2-09 [Modbus Register 2 Address Select]
.
■
H2-20: Comparator 1 Monitor Selection
No.
(Hex.)
Name
Description
Default
(Range)
H2-20
(1540)
Comparator 1 Monitor
Selection
Sets the monitor number for comparator 1. Set the
x-xx
part of the
Ux-xx [Monitor]
. For example, set
H2-20 = 102
to monitor
U1-02 [Output Frequency]
.
102
(000 - 999)
Note:
•
For information on the comparator function, refer to
and
•
The configurable monitor changes when the control method changes.
■
H2-21: Comparator 1 Lower Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-21
(1541)
Comparator 1 Lower Limit
Sets the lower limit detection level for comparator 1 when the full scale analog output for the monitor
selected in
H2-20 [Comparator 1 Monitor Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-22: Comparator 1 Upper Limit
No.
(Hex.)
Name
Description
Default
(Range)
H2-22
(1542)
Comparator 1 Upper Limit
Sets the upper limit detection level for comparator 1 when the full scale analog output for the monitor
selected in
H2-20 [Comparator 1 Monitor Selection]
is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
For information on the comparator function, refer to
and
■
H2-23: Comparator 1 Hysteresis
No.
(Hex.)
Name
Description
Default
(Range)
H2-23
(1543)
Comparator 1 Hysteresis
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the
monitor selected in
H2-20 [Comparator 1 Monitor Selection]
.
0.0%
(0.0 - 10.0%)
Note:
For information on the comparator function, refer to
and
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...