2.8 H: Terminal Function Selection
296
YASKAWA
TOEPYAIGA5002A GA500 Programming
–
The lower limit value of the analog input is higher than the setting value of
d2-02
Note:
Refer to
d4-01: Freq Reference Hold Selection on page 234
for more information.
shows an example of how Up/Down command operates. In this example, the lower limit value of the
frequency reference is set in
d2-02
.
shows the time chart when Freq Reference
Retention Select [d4-01]
is
enabled and disabled.
Figure 2.64 Up/Down Command Time Chart
■
11: Down Command
Setting Value
Function
Description
11
Down Command
Sets the command to use a push button switch to decrease the drive frequency reference. You must also set
Setting 10 [Up
Command]
.
ON : Decreases the frequency reference.
OFF : Holds the current frequency reference.
Note:
•
If you set only the Up command or only the Down command, the drive will detect
oPE03 [Multi-Function Input Setting Err]
.
•
If you set two or more of these functions at the same time, the drive will detect
oPE03
:
–
Up/Down command
–
Accel/Decel Ramp Hold
–
Reference Sample Hold
–
Offset Frequency 1, 2, 3 addition
–
Up/Down 2 Command
•
The Up/Down command does not function in these conditions:
–
b1-01 = 2, 3 [Frequency Reference Selection 1 = Memobus/Modbus Communications, Option PCB]
–
b1-02 ≠ 1 [Run Command Selection 1 ≠ Control Circuit Terminal]
–
Drive is in LOCAL mode
–
Set to
b1-15 [Frequency Reference Selection 2]
by use of
H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection]
When you enter the UP command, the frequency reference increases. When you enter the Down command, the
frequency reference decreases.
The Up and Down commands have priority over all other frequency references. When you enable the Up/Down
command, the drive will ignore these frequency references:
•
Frequency reference from Keypad
[b1-01 = 0]
•
Frequency reference from Analog Input
[b1-01 = 1]
•
Frequency reference from Pulse Train Input
[b1-01 = 4]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...