1.19 Parameters that Change from the Default Settings with E3-01 [Motor 2 Control Mode Selection]
112
YASKAWA
TOEPYAIGA5002A GA500 Programming
1.19
Parameters that Change from the Default Settings with
E3-01 [Motor 2 Control Mode Selection]
The values for the parameters in these tables depend on the values for parameter
E3-01
. When you change the setting
for
E3-01
, the default settings will change.
No.
Name
Range
Unit
Motor 2 Control Method (setting value of E3-01)
V/f
(0)
OLV
(2)
C3-21
Motor 2 Slip Compensation Gain
0.0 - 2.50
0.1
0.0
1.0
C3-22
Motor 2 Slip Comp Delay Time
0 - 10000
1 ms
2000
200
E3-04
Motor 2 Maximum Output
Frequency
40.0 - 590.0
0.1 Hz
60.0
60.0
E3-05
Motor 2 Maximum Output Voltage
0.0 - 255.0
0.1 V
200.0
200.0
E3-06
Motor 2 Base Frequency
0.0 - 590.0
0.1 Hz
60.0
60.0
E3-07
Motor 2 Mid Point A Frequency
0.0 - 590.0
0.1 Hz
3.0
3.0
E3-08
Motor 2 Mid Point A Voltage
0.0 - 255.0
0.1 V
15.0
11.0
E3-09
Motor 2 Minimum Output
Frequency
0.0 - 590.0
0.1 Hz
1.5
0.5
E3-10
Motor 2 Minimum Output Voltage
0.0 - 255.0
0.1 V
9.0
2.0
E3-11
Motor 2 Mid Point B Frequency
0.0 - 590.0
Determined by o1-04
0.0
0.0
E3-12
Motor 2 Mid Point B Voltage
0.0 - 255.0
0.1 V
0.0
0.0
E3-13
Motor 2 Base Voltage
0.0 - 255.0
0.1 V
0.0
0.0
*1
This is the value for 200 V class drives. Double the value for 400 V class drives.
Содержание GA500 series
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Страница 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...