12
YASKAWA
TOEP C710617 0SA YASKAWA AC Drive GA500 Installation Manual
◆
Installation Position and Clearances
Use the clearances specified in
to install the drive. Make sure that there is sufficient
space for wiring and airflow.
Tightly push the drive heatsink plate against the metal surface (enclosure panel) for correct
thermal transfer between the drive and the metal surface.
Note:
You cannot install finless-type drives side-by-side.
A - 30 mm (1.18 in) minimum
B - 100 mm (3.94 in) minimum
C - Metal surface (enclosure panel)
Figure 5.3 Installation Clearances
◆
Drive Watt Loss
■
Heavy Duty Rating (HD): Carrier Frequency = 2 kHz
Table 5.5 Single-Phase 200 V Class (Finless-Type Drive)
Drive Model
Rated Output
Current
(A)
Carrier
Frequency
(kHz)
Drive Watt Loss (W)
Interior Unit
Loss
Heatsink Plate Loss
(P
Loss
)
Total
Loss
B001
0.8
2
7
4
11
B002
1.6
2
10
7
17
B004
3
2
13
13
26
B006
5
2
17
23
40
B010
8
2
30
37
67
B012
11
2
40
48
88