14
YASKAWA
TOEP C710617 0SA YASKAWA AC Drive GA500 Installation Manual
Drive Model
Rated Output
Current
(A)
Carrier
Frequency
(kHz)
Drive Watt Loss (W)
Interior Unit
Loss
Heatsink Plate Loss
(P
Loss
)
Total
Loss
B010
8
8
31
42
73
B012
11
8
41
55
96
Table 5.9 Three-Phase 200 V Class (Finless-Type Drive)
Drive Model
Rated Output
Current
(A)
Carrier
Frequency
(kHz)
Drive Watt Loss (W)
Interior Unit
Loss
Heatsink Plate Loss
(P
Loss
)
Total
Loss
2001
0.8
10
6
5
11
2002
1.6
10
7
8
15
2004
3.0
10
10
16
26
2006
5.0
10
14
27
41
2008
6.9
8
15
35
50
2010
8.0
8
18
43
61
2012
11.0
8
24
56
80
2018
14.0
8
30
82
112
2021
17.6
8
40
108
148
Table 5.10 Three-Phase 400 V Class (Finless-Type Drive)
Drive Model
Rated Output
Current
(A)
Carrier
Frequency
(kHz)
Drive Watt Loss (W)
Interior Unit
Loss
Heatsink Plate Loss
(P
Loss
)
Total
Loss
4001
1.2
8
9
11
20
4002
1.8
8
11
16
27
4004
3.4
8
15
31
46
4005
4.8
8
18
42
60
4007
5.6
8
18
49
67
4009
7.3
8
25
65
90
4012
9.2
8
32
85
117