38
YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Model
Terminal
Recommended
Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
(mm
2
)
IP20 Applicable Gauge
AWG, kcmil
(mm
2
)
Wire Stripping
mm
Terminal Screw
Size and Shape
Tightening Torque
N
∙
m (lbf
∙
in)
4414
R/L1, S/L2, T/L3
250 × 2
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
31.5 - 35
(279 - 310)
U/T1, V/T2, W/T3
300 × 2
2/0 - 300 × 2P
(70 - 150 × 2P)
250 - 300 × 2P
(120 - 150 × 2P)
-
M12
31.5 - 35
(279 - 310)
-, +1
350 × 2
4/0 - 400 × 2P
(95 - 185 × 2P)
300 - 400 × 2P
(150 - 185 × 2P)
-
M12
31.5 - 35
(279 - 310)
1/0
1 - 350
(50 - 185)
-
-
M12
32 - 40
(283 - 354)
4477
R/L1, S/L2, T/L3
3/0 × 4
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
31.5 - 35
(279 - 310)
U/T1, V/T2, W/T3
3/0 × 4
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
31.5 - 35
(279 - 310)
-, +1
4/0 × 4
3/0 - 400 × 4P
(95 - 185 × 4P)
300 - 400 × 4P
(150 - 185 × 4P)
-
M12
31.5 - 35
(279 - 310)
2/0
2/0 - 300
(70 - 150)
-
-
M12
32 - 40
(283 - 354)
4515
R/L1, S/L2, T/L3
4/0 × 4
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
31.5 - 35
(279 - 310)
U/T1, V/T2, W/T3
4/0 × 4
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
31.5 - 35
(279 - 310)
-, +1
250 × 4
3/0 - 400 × 4P
(95 - 185 × 4P)
300 - 400 × 4P
(150 - 185 × 4P)
-
M12
31.5 - 35
(279 - 310)
2/0
2/0 - 300
(70 - 150)
-
-
M12
32 - 40
(283 - 354)
4590
R/L1, S/L2, T/L3
4/0 × 4
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
31.5 - 35
(279 - 310)
U/T1, V/T2, W/T3
250 × 4
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
31.5 - 35
(279 - 310)
-, +1
300 × 4
3/0 - 400 × 4P
(95 - 185 × 4P)
300 - 400 × 4P
(150 - 185 × 4P)
-
M12
31.5 - 35
(279 - 310)
3/0
2/0 - 300
(70 - 150)
-
-
M12
32 - 40
(283 - 354)
4720
R/L1, S/L2, T/L3
300 × 4
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
31.5 - 35
(279 - 310)
U/T1, V/T2, W/T3
300 × 4
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
31.5 - 35
(279 - 310)
-, +1
400 × 4
3/0 - 400 × 4P
(95 - 185 × 4P)
300 - 400 × 4P
(150 - 185 × 4P)
-
M12
31.5 - 35
(279 - 310)
4/0
2/0 - 300
(70 - 150)
-
-
M12
32 - 40
(283 - 354)
*1
The metric wire gauge values are provided as reference information from equivalent AWG sizes and not exactly the same sizes as the
AWG/kcmil values. Obey local safety regulations for wire sizes and make sure that the ferrule or crimp terminals are correct for your size.
*2
For IP20 protection, use wires that are in the range of applicable gauges.
*3
Remove insulation from the ends of wires to expose the length of wire shown.
◆
Main Circuit Terminal Block Wiring Procedure
DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below 50
Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.