14
YASKAWA
TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Item
Specification
Surrounding Area
Pollution degree 2 or less
Install the drive in an area without:
•
Oil mist, corrosive or flammable gas, or dust
•
Metal powder, oil, water, or other unwanted materials
•
Radioactive materials or flammable materials, including wood
•
Harmful gas or fluids
•
Salt
•
Direct sunlight
Altitude
1000 m (3281 ft) maximum
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 m to 4000 m (3281 ft to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
•
When you install the drive at 2000 m (6562 ft) or lower
•
When you install the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and ground the neutral point on the power supply.
Vibration
•
10 Hz to 20 Hz: 1 G (9.8 m/s
2
, 32.15 ft/s
2
)
•
20 Hz to 55 Hz:
2011 to 2031, 4005 to 4034: 0.6 G (5.9 m/s
2
, 19.36 ft/s
2
)
2046 to 2396, 4040 to 4720: 0.2 G (1.96 m/s
2
, 6.43 ft/s
2
)
Installation
Orientation
Install the drive vertically for sufficient airflow to cool the drive.
Table 5.4 Standard
Item
Specification
Harmonized Standard
•
UL 508C
•
EN 61800-3
•
IEC/EN 61800-5-1
•
Two Safe Disable inputs and one EDM output according to EN ISO 13849-1:2015 (PL e (Cat.III)), IEC/EN 61508 SIL3
Table 5.5 Enclosure Ratings
Item
Specification
Protection Design
IP20/UL Open Type
IP20/UL Type 1
IP55/UL Type 12
IP55/UL Type 12 Heatsink External Mounting
Note:
Install a UL Type 1 kit on an IP20/UL Open Type drive to convert the drive to an IP20/UL Type 1.
◆
Area of Use
Install this product in a location with Overvoltage Category III and pollution degree 2 or less.
■
Ambient Temperature Setting
Maintain the ambient temperature within the following ranges according to the enclosure type.
•
IP20/UL Open Type/Heatsink External Mounting: -10 °C to +50 °C (14 °F to 122 °F)
•
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
•
IP55/UL Type 12 Heatsink External Mounting; front side: -10 °C to +50 °C (14 °F to 122 °F)
•
IP55/UL Type 12 Heatsink External Mounting; back side: -10 °C to +40 °C (14 °F to 104 °F)
6
Mechanical Installation
This section gives information about the standard environment for correct installation.
◆
Moving the Drive
Obey local laws and regulations when moving and installing this product.
CAUTION
Crush Hazard. Tighten terminal cover screws and hold the case safely when you move the drive. If the drive or
covers fall, it can cause moderate injury.