TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Figure 10.8 Locations of Switches
Table 10.8 I/O Terminals and Switches Functions
Position
Switch
Terminal
Function
Default Setting
A
Jumper switch S1
A1, A2, A3
Sets terminals A1 to A3 to voltage or current output.
A1: V (voltage input)
A2: I (current input)
A3: V (voltage input)
B
Jumper switch S5
FM, AM
Sets terminals FM and AM to voltage or current output.
FM: V (voltage output)
AM: V (voltage output)
C
DIP switch S2
-
Enables and disables the termination resistor of MEMOBUS/
Modbus communications.
OFF
◆
Control I/O Connections
This section gives information about the settings for the listed control circuit I/O signals.
•
MFDI (terminals S1 to S8)
•
MFDO (terminals M1 to M4 and MD to MF)
•
MFAI (terminals A1 to A3)
•
MFAO (terminals FM, AM)
•
MEMOBUS/Modbus communications (terminals D+, D-, AC)
■
Set Sinking Mode/Sourcing Mode
Close the circuit between terminals SC-SP and SC-SN to set the sinking mode/sourcing mode and the internal/
external power supply for the MFDI terminals. The default setting for the drive is internal power supply sinking
mode.