12  MEASURES TO SATISFY THE EMC DIRECTIVES

E-15

„

Wiring Examples

The following diagrams show the wiring example.  Before wiring, turn OFF the Power ON/
OFF switch and post a notice of “No Conduction.”  Only an electrical expert can perform the 
wiring.  The noise filter and the core are shown in the diagram.

Note: 1. Clamp: Secure and ground cable shields using conductive metal parts.

2. Make sure that the grounding plate are securely connected to the grounding.
3. Remove the paint from the grounding plate to insure a good connection with filter, SER-

VOPACK, clamp, etc.

<REQUIRED EMC SPECIFICATIONS>

Grounding plate/Box

Three-phase

400 VAC

Single-phase

200 VAC

Clamp

Noise

filter 1

Noise

filter 2

AC/DC

converter

CN1

Core

Core

Core

Core

Core

Core

Core

Open

Moter

Servomotor

Host controller

Encoder

Core

Core

Clamp

Clamp

Clamp

Clamp

Core

Control box

NS115

SGDH

SERVOPACK

L1, L2, L3

A1, A2

CN6A

CN6B

U, V, W,

CN2

Clamp

Main

power

supply

Control

power

supply

Содержание E-II Series

Страница 1: ...P NS115 Applicable SERVOPACK Model SGDH E MECHATROLINK II Application Module II Series AC Servo Drives SAFETY PRECAUTIONS To properly use the product read this manual thoroughly and retain for easy re...

Страница 2: ...liability is assumed with respect to the use of the information contained herein Moreover because Yaskawa is constantly striving to improve its high quality products the information contained in this...

Страница 3: ...ore operating this product Some drawings in this manual are shown as typical example and may differ from the shipped product This manual may be modified when necessary because of improvement of the pr...

Страница 4: ...in a serious accident In either case follow these important items Indicates prohibited actions that must not be performed For example this symbol would be used to indicate that fire is prohibited as...

Страница 5: ...achine not only damage the machine but may also cause an accident resulting in death or injury Do not remove the terminal cover cables connectors or optional items while the power is ON Failure to obs...

Страница 6: ...king materials must be treated before the product is packaged and meth ods other than fumigation must be used Example Heat treatment where materials are kiln dried to a core temperature of 56 C for 30...

Страница 7: ...serve this caution may result in fire Do not bundle or run power and signal lines together in the same duct Keep power and signal lines separated by at least 30 cm Use twisted pair shielded wires or m...

Страница 8: ...t When disposing of the products treat them as ordinary industrial waste CAUTION CAUTION Check Items Remarks Check if the delivered products are the ones you ordered Check the types marked on the name...

Страница 9: ...lectric shock Do not touch heat sink when power is ON May cause burn Use proper grounding techniques 5 WARNING CAUTION NS115 Module warning label position Warning Label and Grounding Mark Position SGD...

Страница 10: ...washer Use attached screws on the NS115 Module SGDH 60 to 1EAE SGDH 60 to 1EDE M4 8 round head screws with spring washer and plain washer Use the screw of the front panel Rack mounted SGDH A3 to 02BE...

Страница 11: ...the NS115 Module to the terminal marked G on the SERVOPACK CN10 Connector to SERVOPACK SGDH SERVOPACK YASKAWA 5 Ground wire G For the SERVOPACK 30 W to 5 0 kW MODE SET DATA CHARGE POWER SGDH SERVOPAC...

Страница 12: ...onvection so that the temperature around the periphery of the SERVOPACK does not exceed 55 C When installed near a source of vibration Install a vibration isolator underneath the SERVOPACK to prevent...

Страница 13: ...thod Environments in Control Panel Maintain the following conditions inside the control panel Ambient temperature for SERVOPACK 0 to 55 C Humidity 90 RH or less Vibration 4 9 m s2 Condensation and fre...

Страница 14: ...table shows the NS115 Module general specifications Item Frequency Procedure Remedy Clean unit interior and circuit boards At least once a year Check for dust dirt and oil on surfaces Clean with comp...

Страница 15: ...able For fully closed encoder CN4 connector use the following connector Use the twisted pair shielded cable Connector 54306 2011 Made by Molex Japan Connector case 54331 0201 Made by Molex Japan The C...

Страница 16: ...e shield using a piece of conductive metal Example of Cable Clamp SERVOPACK side Ground plate Cable Cable Clamp Shield cable sheath stripped Remove paint on mounting surface Fix and ground the cable s...

Страница 17: ...arts 2 Make sure that the grounding plate are securely connected to the grounding 3 Remove the paint from the grounding plate to insure a good connection with filter SER VOPACK clamp etc REQUIRED EMC...

Страница 18: ...Road HuangPu District Shanghai 200003 China Phone 86 21 5385 2200 Fax 86 21 5385 3299 YASKAWA ELECTRIC SHANGHAI CO LTD BEIJING OFFICE Room 1011 Tower W3 Oriental Plaza No 1 East Chang An Ave Dong Chen...

Отзывы: