6 DeviceNet Option Drive Parameters
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
15
6
DeviceNet Option Drive Parameters
Confirm proper setting of the all parameters in
before starting network communications.
Table 8 Parameter Settings
No.
(Addr.
Hex)
Name
Description
Values
b1-01
(180)
Frequency Reference Selection
Selects the frequency reference input source
0: Digital Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
Default: 1
Range: 0~4
(Set to 3 for DeviceNet only)
b1-02
(181)
Run Command Selection
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option PCB
Default: 1
Range: 0~3
(Set to 3 for DeviceNet only)
F6-01
(3A2)
Operation Selection after
Communications Error
Determines drive response when a bUS error is detected during
communications with the DeviceNet Option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Default: 1
Range: 0~3
F6-02
(3A3)
External Fault Detection Conditions
(EF0)
Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation
Default: 0
Range: 0~1
F6-03
(3A4)
Stopping Method for External Fault
from Communication Option
Determines drive response for external fault input (EF0)
detection during DeviceNet communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Default: 1
Range: 0~3
F6-06
Torque Reference/Torque Limit
Selection from Communications
Option
0: Torque reference / torque limit via network communications
are disabled.
1: Torque reference / torque limit via network communications
are enabled.
0
F6-07
(3A8)
NetRef/ComRef Selection Function
0: Multi-step speed reference disabled (F7 mode)
1: Multi-step speed reference allowed (V7 mode)
Default: 0
F6-08
(36A)
Reset Communication Related
Parameters
Determines which F6-
and F7-
parameters are reset to
default values when the drive is initialized using A1-03.
0: Do not reset parameters
1: Reset parameters
Default: 0
F6-50
(3C1)
MAC ID
Selects the drive MAC address
Note:
Used in the DeviceNet Object
Default: 0
Range: 0~64
F6-51
(3C2)
Baud Rate
DeviceNet communication speed
0: 125 k bit/s
1: 250 k bit/s
2: 500 k bit/s
3: Programable from Network
4: Detect automatically
Note:
Used in the DeviceNet Object
Default: 0
Range: 0~4
F6-52
(3C3)
PCA setting
I/O Polled Consuming Assembly data instance
Note:
Used in the Connection Object
Default: 21
Range: 0~255
F6-53
(3C4)
PPA setting
I/O Polled Producing Assembly data instance
Note:
Used in the Connection Object
Default: 71
Range: 0~255
F6-54
(3C5)
Idle Mode Fault Detection Selection
When detection is enabled and idle messages are detected, the
option will set Run and Frequency to 0.
0: Detection enabled
1: No detection
Default: 0
Range: 0~1