11.11 o: Keypad-Related Settings
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
787
■
o1-44: 2nd Monitor Area Setting
No.
(Hex.)
Name
Description
Default
(Range)
o1-44
(11C4)
RUN
2nd Monitor Area Setting
Sets the horizontal axis value used to display the monitor set in
o1-25 [Custom Monitor 2]
as a
bar graph. This parameter is only available with an LCD keypad.
100.0%
(0.0 - 100.0%)
■
o1-45: 3rd Monitor Area Selection
No.
(Hex.)
Name
Description
Default
(Range)
o1-45
(11C5)
RUN
3rd Monitor Area Selection
Sets the horizontal axis value used to display the monitor set in
o1-26 [Custom Monitor 3]
as a
bar graph. This parameter is only available with an LCD keypad.
0
(0 - 1)
0 : +/- Area ( - o1-46
~
o1-46 )
1 : + Area ( 0 ~ o1-46 )
■
o1-46: 3rd Monitor Area Setting
No.
(Hex.)
Name
Description
Default
(Range)
o1-46
(11C6)
RUN
3rd Monitor Area Setting
Sets the horizontal axis value used to display the monitor set in
o1-26 [Custom Monitor 3]
as a
bar graph. This parameter is only available with an LCD keypad.
100.0%
(0.0 - 100.0%)
■
o1-47: Trend Plot 1 Scale Minimum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-47
(11C7)
RUN
Trend Plot 1 Scale
Minimum Value
Sets the minimum value for the vertical axis used to display a trend plot from the monitor selected
with
o1-24
. This parameter is only available with an LCD keypad.
-100.0%
(-300.0 - +99.9%)
■
o1-48: Trend Plot 1 Scale Maximum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-48
(11C8)
RUN
Trend Plot 1 Scale
Maximum Value
Sets the maximum value for the vertical axis used to display the monitor that was set in
o1-24
[Custom Monitor 1]
as a trend plot. This parameter is only available with an LCD keypad.
100.0%
(-299.9 - +300.0%)
Note:
Parameter
o1-47 [Trend Plot 1 Scale Minimum Value]
sets the lower limit. The lower limit is (
o1-47
+ 0.1)%.
■
o1-49: Trend Plot 2 Scale Minimum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-49
(11C9)
RUN
Trend Plot 2 Scale
Minimum Value
Sets the minimum value for the vertical axis used to display a trend plot from the monitor selected
with
o1-25
. This parameter is only available with an LCD keypad.
-100.0%
(-300.0 - +99.9%)
■
o1-50: Trend Plot 2 Scale Maximum Value
No.
(Hex.)
Name
Description
Default
(Range)
o1-50
(11CA)
RUN
Trend Plot 2 Scale
Maximum Value
Sets the maximum value for the vertical axis used to display the monitor that was set in
o1-25
[Custom Monitor 2]
as a trend plot. This parameter is only available with an LCD keypad.
100.0%
(-299.9 - +300.0%)
Note:
Parameter
o1-49 [Trend Plot 2 Scale Minimum Value]
sets the lower limit. The lower limit is (
o1-49
+ 0.1)%.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...