SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
721
Note:
Refer to
“
H2-06: Watt Hour Output Unit Selection
”
for more information.
■
3C: LOCAL Control Selected
Setting Value
Function
Description
3C
LOCAL Control Selected
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
The keypad is the Run command source or the frequency reference source.
OFF : REMOTE
The Run command source or frequency reference source is an external source set with
b1-01 [Frequency
Reference Selection 1]
,
b1-15 [Frequency Reference Selection 2]
,
b1-02 [Run Command Selection 1]
, or
b1-16
[Run Command Selection 2]
.
■
4C: During Fast Stop
Setting Value
Function
Description
4C
During Fast Stop
The terminal activates when the fast stop is in operation.
■
4D: oH Pre-Alarm Time Limit
Setting Value
Function
Description
4D
oH Pre-Alarm Time Limit
The terminal activates when
L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and
oH [Heatsink
Overheat]
does not clear after the drive decreases the frequency for 10 cycles.
Note:
Refer to
“
L8-03: Overheat Pre-Alarm Ope Selection
”
for more information about drive derating operation.
■
4E: Braking Transistor Fault (rr)
Setting Value
Function
Description
4E
Braking Transistor Fault
(rr)
The terminal activates when the internal braking transistor overheats and the drive detects an
rr [Dynamic Braking Transistor
Fault]
fault.
■
4F: Braking Resistor Overheat (rH)
Setting Value
Function
Description
4F
Braking Resistor Overheat
(rH)
The terminal activates when the braking resistor overheats and the drive detects an
rH [Braking Resistor Overheat]
fault.
The braking resistor overheats when the deceleration time is short and there is too much motor regeneration
energy.
■
51: Safe Torque OFF
Setting Value
Function
Description
51
Safe Torque OFF
The terminal turns on (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and when
terminals H1-HC and H2-HC are off (released).
Note:
EDM = External Device Monitor
ON : Safety stop state
Both terminal H1-HC and H2-HC have been turned off, or released (safety stop state).
OFF : Safety circuit fault or RUN/READY
Either terminal H1-HC or H2-HC has been turned OFF, or released (safety circuit fault), or both of these terminals
are ON, or have short circuited (RUN/READY).
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...