SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
3 : Option PCB
Use a communications option card or input option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If
b1-02 = 3
but no connected option card, then
oPE05 [Run Cmd/Freq Ref Source Sel Err]
will flash on the keypad.
■
b1-03: Stopping Method Selection
No.
(Hex.)
Name
Description
Default
(Range)
b1-03
(0182)
Stopping Method Selection
Sets the method to stop the motor after removing a Run command or entering a Stop command.
0
(0 - 3)
Note:
The setting range is 0, 1, and 3 when
A1-02 = 3, 4 [Control Method Selection = Closed Loop Vector, Advanced Open Loop Vector]
.
Select the appropriate stopping method for the application from the following four options.
0 : Ramp to Stop
The drive decelerates the motor to stop when the Stop command is entered (or when the Run command is
switched OFF).
The drive ramps the motor to stop according to the deceleration time. The default setting for the deceleration time
is
C1-02 [Deceleration Time 1]
. The actual deceleration time will vary depending on load conditions, such as
mechanical loss and inertia.
If the output frequency falls below or is equal to the value set in
b2-01 [DC Injection/Zero SpeedThreshold]
during deceleration, then the drive will perform DC Injection Braking, or Zero Speed Control, depending on the
control mode.
•
Ramp to stop with V/f control, Advanced Open Loop Vector Control, Closed Loop V/f Control, Open Loop
Vector Control Mode
Parameter
b2-01
sets the frequency to begin DC Injection Braking at stop. If the output frequency falls below or
is equal to the value set in
b2-01
during deceleration, then the drive will perform DC Injection Braking for the
time set in
b2-04 [DC Inject Braking Time at Stop]
.
Figure 11.9 Ramping to Stop in V/f, CL-V/f, or OLV
Note:
The drive will begin DC Injection Braking from the frequency set in
E1-09 [Minimum Output Frequency]
if
b2-01 ≤ E1-09
.
•
Ramping to Stop in Closed Loop Vector Control
Parameter
b2-01
sets the frequency to begin Zero Speed Control at stop. If the output frequency falls below or is
equal to the value set in
b2-01
during deceleration, then the drive will perform Zero Speed Control for the time
set in
b2-04
.
Figure 11.10 Ramping to Stop in Closed Loop Vector Control
V/f
CL-V/f
OLV
CLV
AOLV
Содержание CR700
Страница 1: ......
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Страница 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Страница 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...